Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 24
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Table 13: Diagnostic Reports
Report Selections
Report
Description
R# SDI Dev Fail
1
Yes, No
SDI device
failure
R# SDI Dev Restl Yes, No
Restoral of SDI
device failure
R# Watchdog
Rset
Yes, No
Watchdog
Reset Event
R#
ParaChksmFail
Yes, No
Parameter
checksum
failure
R# Reboot Yes, No Reboot Event
R# Ph Line Fail
1
Yes, No
Failure of phone
line
R# Ph Line Rstl Yes, No
Restoral of
phone line after
failure
R# AC Fail
1, 2
Yes, No
Failure of AC
power to control
panel
R# AC Restorl
2
Yes, No
Restoral of AC
power to control
panel after
failure
R# Batt Missing
1, 2
Yes, No
Battery Missing
Detection Event
R# Battery Low
1, 2
Yes, No
Low battery
power
R# Battery Rstl
2
Yes, No
Restoral of
battery power to
control panel
after Missing or
Low Event
R# Rt Comm Fail
1,
3
Yes, No
Failure to send
report to
specific route
R# Rt Comm Rstl Yes, No
Restoral of
communication
to specific route
after a failure
Table 13: Diagnostic Reports (Continued)
Report Selections
Report
Description
R# Rt Comm Rstl Yes, No
Restoral of
communication
to specific
route after a
failure
R# Checksum Fail Yes, No
Checksum Fail
Event
R# Network Fail
4
Yes, No
Failure of
network
R# Network Rest
4
Yes, No
Restoral of
network
R# Network Cond
4
Yes, No
Condition of
network
1
This event is included in the Expanded Test Report
when an off-normal condition exists.
2
To meet UL 864 requirements for Central Station and
Remote Station applications, enable AC Fail, Battery
Missing, Low Battery, Battery Restoral, and AC
Restoral reports.
3
This event covers Comm Fail Route Group and Comm
Fail Phone. If enabled, both events are sent; if
disabled, neither event is sent.
4
This event is reserved for future use.
Enable Rt Comm Fail and Rt Comm
Restore in only one route group.
Relay Reports
Selecting Yes enables sending a report when the
event occurs.
Table 14: Relay Reports
Report Selections
Report
Description
R# Sensor
Reset
Yes, No
Sensor Reset
Event
R# Relay Set Yes, No Relay Set Event
R# Relay
Reset
Yes, No Relay Reset Event