D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 21
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
2.3.9 Route Group Categories
Fire Reports
To meet UL 864 requirements for
Central Station and Remote Station
applications, enable Fire Reports.
Selecting Yes enables a report to be sent when the
event occurs.
Table 9: Fire Reports
Report Selections
Report
Description
R# Fire Alarm Yes, No Fire Event
R# Fire
Restore
(Alarm)
Yes, No
Fire restoral from
alarm
R# Fire
Missing
Yes, No Missing Fire point
R# Fire
Trouble
Yes, No Fire trouble
R# Fire
Supervis
Yes, No Fire supervision
R# Fire
Restore
(T/M/S)
Yes, No
Fire restoral from
trouble, missing, or
bypass
R# Fire
Cancel
Yes, No Canceled fire alarm
R# Fire Sup
Miss
Yes, No
Fire supervisory
missing
R# Fire Supv
Rest
Yes, No
Restorals from Fire
Supervision
Burglar Reports
Select Yes to send a report when the event occurs.
Refer to Table 10 on page 21.
Table 10: Burglar Reports
Report Selections Report Description
R# Alarm Yes, No Burglar Alarm Event
R# Burg
Restore
Yes, No
Non-fire restoral from
trouble, missing, or
supervisory
R# Duress Yes, No Duress
R# Missing
Alarm
Yes, No Missing Alarm point
R# Usr Code
Tmpr
Yes, No User code tamper
R# Trouble
Report
Yes, No Trouble Event
R# Missing
Trbl
Yes, No
Missing Trouble
Event
R# Non Fire
Suprv
Yes, No
Non-fire Supervision
Event
R# Pt Bus
Fail
Yes, No Point bus failure
R# Pt Bus
Rstl
Yes, No
Restoral of point bus
after failure
R# Non Fire
Cncl
Yes, No
Canceled non-fire
alarm
R# Alarm
Restore
Yes, No
Non-fire restoral from
alarm
R# Sup
Missing
Yes, No Supervisory missing
R# Unverified
Evt
Yes, No
Unverified Events for
Cross Points
R# Unverified Evt is sent when a single
point programmed in Cross Point Group
faults into an alarm condition, then
restores before the Cross Point Time
elapses.
R# Unverified Evt encompasses both
Fire and Non-fire points, but is not related
to the A# Verify Time used for smoke
detectors.
The GV3 Series control panels log a
Ground Fault Event as Trouble Point 256.
Restoral Reports are not sent if the
control panel resets after a point is
bypassed and then unbypassed. This is
true for both Fire and Non-fire points.