5.4.1 Configuration for RPS Over Network
COMMAND 43 (Remote Programming) can establish
communication with RPS over the phone or over the
network. Figure 6 on page 128 and Figure 7 on page
129 show the structure of COMMAND 43.
Answer RPS Over Network
Default: Yes
Selection: Yes or No
Yes
Enable automatic answer of RPS
initiated sessions over the network.
No
Do not automatically answer RPS
initiated sessions over the network.
This prompt determines if the control panel
automatically answers RPS initiated sessions through
a network interface module on the SDI bus.
This prompt can be momentarily disabled by
selecting ALLOW ANSWER through COMMAND 43
(Remote Programming) menu (refer to Figure 6 on
page 128 and Figure 7 on page 129).
If the Reset switch (labeled S1) label is in
the locked position, network RPS
programming is allowed even if this
prompt is set to No.
RPS Address Verification
Default: No
Selection: Yes or No
Yes
Verifies that the incoming RPS IP
address matches the address
entered in RPS IP Address.
No Do not verify the RPS IP address.
Allow RPS to connect to the control
panel from any network source .
When enabled, this feature will verify that the Remote
Programming Software connecting to the control
panel is coming from a known IP address. This
verification can be momentarily disabled by selecting
ALLOW ANSWER through COMMAND 43 (Remote
Programming) menu (refer to Figure 6 on page 128