Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 12
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
2.0 Panel and Area Wide
Parameters
This section has twelve programming categories:
Phone
Phone Parameters
Routing
Area Parameters
Power Supervision
Printer Parameters
RPS Parameters
Miscellaneous
Area Parameters
Keypad
User Interface
Function List
Relay Parameters.
2.1 Phone
The control panel can dial as many as four different
telephone numbers when sending event reports.
Refer to Section 2.3 Routing on page 17 for
information about event report routing and
communication protocols.
When using PSTN telephone lines,
program two telephone numbers to
meet UL 864 requirements.
Phone #
Default: Blank
Selection:
Up to 24 characters
0 to 9 Numbers 0 through 9
C 3-sec pause
D 7-sec dial-tone detection
# or * Used for the same purpose as
pressing this key on a telephone
keypad when manually dialing. For
example, an asterisk (*) may be
needed to access your long distance
service. Do not use these characters
when pulse dialing.
Blank Control panel dials no phone number.
Programming this item Blank does
not disable phone routing. To disable
reporting to this phone, refer to
Section 2.3 Routing on page 17.
This is the telephone number the control panel dials to
contact the central station receiver when sending
event reports. This number is Phone 1 referred to in
the prompts in Section 2.3 Routing on page 17.
The control panel waits for a break in the dial tone
after dialing the first digit. If the control panel must dial
a digit (for example, 9) to access an outside line, place
a C before the phone number. The control panel waits
2 sec and does not wait for the dial tone break.
The control panel is programmed with a 7-sec dial
tone detect period. When a dial tone is detected or the
waiting period ends, the control panel begins to dial.
To extend the dial tone detect period, place a D before
the phone number. To insert a pause during or after
dialing, use C in the number sequence. For example,
if the control panel hangs up before it hears the
Modem IIIa
2
ACK tone from the D6500 or D6600,
program extra Cs after the phone number. The control
panel waits on line for two extra seconds for each C
programmed.
Enter up to 24 of the characters shown in the Phone #
table to define dialing characteristics.
For SIA CP-01 Compliance
Call Waiting Disable
If the telephone system at the installation site uses the
Call Waiting feature, ensure that the primary
telephone reporting number is programmed to disable
Call Waiting.