Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 37
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Area 1 must be enabled:
System events such as power and
phone supervision do not send a
report correctly if Area 1 is disabled.
When programmed No, points
assigned to this area do not generate
events, show at the keypad when
arming and disarming, or send status
reports. All user authority in this area
is turned off while the area is
disabled.
To meet UL 864 requirements, set A#
Area On to Yes.
Area# Account Number
Default: 0000
Selection:
For Modem and Contact ID (four-
digit account numbers): 0000 to
9999,
BBBB to FFFF
For Modem (ten-digit account
numbers): 0000000000 to
9999999999, BBBBBBBBBB to
FFFFFFFFFF
Determines the account number for this area. An
account number must be assigned to each active
area.
Account numbers are used to group areas together.
Each area can have a different account number, or
several areas can share the same account number.
The control panel uses the account number as a
reference for arming and keypad text displays.
Contact ID: Only the last four digits are sent.
Modem IIIa
2
: Enter a four-digit or ten-digit number.
Keypad Programming of Area # On and Area#
Account Number
D1255
1. Refer to Figure 1 on page 7 to access Keypad
Programming and navigate to the AREA
PARAMETERS option. Press [ENT].
2. The keypad reads AREA NUM 1 – 32 (1 – 8 for
the D7412GV3).
3. Enter the area number you wish to configure and
press [ENT]. The current area status shows (for
example, AREA 1 ON: YES).
4. Press [ENT] to change the area’s status.
5. Press the [PREV] or [NEXT] button to toggle
between YES and NO, and then press [ENT]
when the desired configuration option shows.
When the keypad reads PARAMETER SAVED, your
selection is configured.
6. When the keypad reads AREA STATUS, press
[NEXT] to advance to the A# ACCOUNT
NUMBER option. The keypad shows the currently
configured account number.
7. Press [ENT] to change the account number.
8. The [PREV] button acts as a [Backspace] key.
The [COMMAND] key cycles though the special
account number characters (B, C, D, E, F);
[NEXT] select the account number character.
Press [PREV] to delete the characters of the
account number and then enter the new account
number.
9. Press [ENT] to save the changes.
When the keypad reads Parameter Saved, your
selection is configured.
D1260
1. Refer to Figure 2 on page 8 to access Keypad
Programming and navigate to the Area
Parameters option. Press [ENT].
2. The keypad reads Area Number 1 – 8.
3. Enter the area number you wish to configure and
press [Enter]. The current area status shows (for
example, Area 1 On: Yes).
4. Press the Edit softkey to change the area’s status.
5. Press the Yes or No
softkey, and then press the
Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection is configured.
6. When the keypad reads Area Status, press the
Account Number softkey. The keypad shows the
currently configured account number.
7. Press the Edit softkey to change the account
number.
8. Use the softkeys and the number buttons on the
keypad to enter the new account number. The
Backspace softkey allows you to erase
characters. The Clear softkey allows you to clear
the entire account number. When entering a letter
character, press the letter's softkey to select it.
The Previous and Next softkeys advance through
the letter characters (A, B, C, D, E, F).
9. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection is configured.
A# Force Arm/Bypass Max
Default: 1
Selection:
0 to 99
Specify the maximum number of combined Controlled
points that can be faulted or bypassed when arming
this area.