Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 116
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Default: 0
Selection: 0 to 24, 28, 29
S## Area 1[through #]
Yes
Unbypass all
points in Area #.
5
Unbypass All Points: This function
is not available as a keypad function.
The entry in the S## Area # prompt
defines the area(s) where the sked
unbypasses all points. The sked
unbypasses all points in the area,
regardless of how they were
bypassed. This sked can unbypass
all points in multiple areas.
Default: No
Selection: Yes or No
Select Yes to unbypass all
points in the areas indicated.
No Do not
unbypass all
points in
Area #.
S## Relay Number
Blank No relay is
activated.
6
Relay On: This function emulates
the Change Relay keypad function to
turn relays on. The entry in the S##
Relay Number prompt defines the
specific relay this sked activates.
The sked can activate one relay.
Default: Blank
Selections: Blank,
1 to 128 for D9412GV3,
1 to 64 for D7412GV3
Enter the number of the relay
the sked activates
1 to 128 Relay to
activate.
S## Relay Number
Blank No relay is
turned off.
7
Relay Off: This function emulates
the Change Relay? keypad function
to turn relays off. The entry in the
S## Relay Number prompt defines
the relay this sked turns off. The
sked can turn off only relays that are
set by a sked. The sked can turn off
one relay.
Default: Blank
Selections: Blank,
1 to 128 for D9412GV3,
1 to 64 for D7412GV3
Enter the number of the relay
that turns the sked off.
1 to 128 Relay to turn off.
8 All Relays Off: This function is not available as a keypad function. This sked function turns off all
relays that are turned on by a sked. This is a panel-wide function.
No other parameters require input for this option.
(Continued on next page.)