D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 142
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Door points must be programmed as
Perimeter points. If a 24-hour point type
is required for the Door point, you can
use a Perimeter point type with a point
response of 9 to C. Also, the debounce
count must be set to 4 in Point
Assignments.
When assigning Points 1 to 8 (control
panel zones), the end-of-line (EOL)
resistors must be removed from the
control panel.
Also, do not enable any POPIT points (or
OctoPOPIT points) sharing the same
point number as the Door point. Failure
to do so results in extra point trouble
conditions upon reboot.
D# Interlock Point
Default: Blank
Selection: 0 to 127, 129 to 247
(0 to 75 on the D7412GV3)
1 to 127,
129 to 247
The point number assigned to the
Interlock point. Points 128 and 248
are reserved by the control panel for
internal use.
0
No point number is assigned to the
Interlock point.
Enter the interlock point number. This point, when
faulted, prevents the door controller from allowing
access upon a valid ID read or door request.
Do not assign this point to another D# Door Point.
You can, however, assign it to another controller to
prevent multiple controllers from activating.
Door points must be programmed as
Perimeter points. If a 24-hour point type is
required for the Door point, you can use a
Perimeter point type with a Point
Response of 9 to C. Also, the debounce
count must be set to 4 in Point
Assignments.
The Interlock point is considered in a
normal state if it is bypassed, swinger
bypassed, or forced armed. This results in
normal access even if the door remains
open.
D# Auto Door?
Default: No
Selection: Yes or No
Yes
When the area assigned in D# Entry
Area # is disarmed, the door is in
the unlocked state. When that area
is armed, the door returns to the
locked state.
No Door state is not affected by the
armed state of the area.
Use this program item to automatically unlock the
door (latched, shunt, and strike) when the entry area
is disarmed. The door re-locks upon Master or
Perimeter Arming the area.
The unlocked state cannot be overridden
manually.
D# Fire Unlock?
Default: No
Selection: Yes or No
Yes
Relay activates and shunt is applied
for the door contact automatically
upon a Fire Alarm.
No
Door remains in its current mode
upon a Fire Alarm.
Use this program item to activate the relay for the
door strike and shunt the door zone automatically
upon a Fire Alarm. This feature overrides a Secure
Door state, Locked Door state, Auto Door, and an
Interlock Faulted point. The relay activates for all
doors with this prompt programmed as Yes when a
Fire Alarm occurs in any area. Relays that are
activated by Fire Unlock can be returned to normal
only through the keypad using the Door Control
function.
Doors that are activated by Fire Unlock
must be returned to normal using the
Door Control function on the keypad.