Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 38
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Refer to the prompts P## Force Arm Returnable
and P## Bypass Returnable in Section 3.2 Point
Responses on page 91 for returning a point to the
system when the point returns to normal or when the
area is disarmed.
Users can bypass more points than the
number entered here during the
disarmed state. It is only when the user
attempts to Bypass Arm an area (or
areas) that this restriction is enforced.
A# Delay Restorals
Default: No
Selection:
Yes or No
Yes Point Restoral Report is not sent until
the bell time expires or user
acknowledges alarm condition.
No Restoral Reports are sent when point
restores, regardless of bell time.
A# Exit Tone
Default: Yes
Selection:
Yes or No
Sounds an exit tone during exit delay at all keypads
assigned to this area.
You can turn off exit tones for individual
keypads by programming the
appropriate CC# 1 to 8 as No in CC#
Exit Tone.
A# Exit Dly Time
Default: 60
Selection:
0 to 600 ( in 5 sec increments)
Exit delay time for this area when Master Exit or
Perimeter Exit arming.
Points programmed for instant alarm
response generate alarms immediately,
even during exit delay. To avoid instant
alarms on points adjacent to the
perimeter when leaving the area,
program P## Type as 3 (Interior
Follower).
For SIA CP-01 Compliance
The Exit Delay Time must be between 45 sec and
255 sec.
A# Auto Watch
Default: No
Selection:
Yes or No
Yes When the area is disarmed, Watch
Mode turns on automatically.
No When the area is disarmed, Watch
Mode must be turned on or off
manually.
Controlled points must be programmed
as P## Watch Point to generate a
watch tone.
A# Verify Time
Default: 60
Selection:
10 to 60 (in 1-sec increments)
Use alarm verification with smoke detectors to reduce
the number of false fire alarms. When Verify Time is
programmed, the control panel can check smoke
detector point activations before generating alarm
signals.
Do not enable the Cross Point feature
in point indexes designated for Fire
points.
Check with your authority having
jurisdiction (AHJ) to determine the
maximum verification time allowed.
Points are programmed individually to activate the
verification feature. Refer to Section 3.1 Point Index
on page 87. Any resettable Fire point can activate
alarm verification for the area to which it is assigned.
Use separate area alarm-verification relays.
To enable alarm verification on a point, program Point
Index, Fire Point, Alarm Verify, and Resettable as
Yes.
When an Alarm Verification point senses an alarm, the
control panel automatically removes power to all
Resettable points connected to the area’s Reset
Sensors relay. The sensor reset removes power to the
sensors for the amount of time programmed in Verify
Time. When power is reapplied, a 60-sec confirmation
window begins. If the detector is still in alarm and
experiences another alarm during the confirmation
window, or a different Resettable Verification point in
the area senses an alarm, an alarm occurs.
Example: Verify Time is set for 20 sec. The alarm
verification cycle starts when the detector senses
smoke or fire. No report occurs.