D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 82
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Comm Fail
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Activates when a control panel cannot communicate
a report after making ten attempts to each routing
destination. At the same time, COMM FAIL RG
displays at the keypad. This relay automatically
resets when a report is sent successfully.
Use this relay to report primary digital
report failure to an alternate
communication device.
Log % Full
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Enter the number of the relay that activates when the
log reaches the programmed percentage of its
capacity as programmed in the Log % Full prompt
under PANEL WIDE PARAMETERS >RPS
Parameters. This relay provides a steady output until
a Get Log and Set Pointer is executed from the
remote programming software (RPS).
Summary Fire
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Enter the number of the relay that activates when any
Fire point in the system (P## Type 0, P## Fire Yes)
enters into alarm. This relay provides a steady output
until all Fire points in the system return to normal.
Refer to Fire Summary Sustain on page 137 for
details on alternate operation.
Summary Alarm
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Enter the number of the relay that activates when a
Non-fire point enters into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid passcode, then cleared from alarm memory with
an acknowledgment at the keypad.
This relay does not activate for silent and
invisible alarms.
Summary Fire Trouble
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Activates when any Fire point in the control panel is
in trouble, or if a Fire Supervision point is missing.
This relay provides a steady output until all Fire
points restore to a normal condition.
Summary SupFire
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off-
normal). This relay provides a steady output until all
Fire Supervisory points are restored to a normal
condition.
Summary Trouble
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Activates when any Non-fire point in the control panel
is in a trouble condition. This relay provides a steady
output until the user at the keypad acknowledges the
trouble.
Summary SupBurg
Default: 0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Activates when any Non-fire Supervisory point in the
control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay provides
a steady output until the user at the keypad
acknowledges the condition.
2.1 Passcode or Token Worksheet
These programming items assign:
a passcode to user groups 001 to 249,
areas by authority level, and
a User Group Window.