Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 20
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
R# Backup Device
Default: No Device
Selection:
No Device, Phone 1..4, SDI ##
Path 1..4
Phone 1 Phone 1 is this group’s backup
destination if the primary
destination fails.
Phone 2 Phone 2 is this group’s backup
destination if the primary
destination fails.
Phone 3 Phone 3 is this group’s backup
destination if the primary
destination fails.
Phone 4 Phone 4 is this group’s backup
destination if the primary
destination fails.
SDI 88 Path 1 Path 1 on SDI 88 is this group's
backup destination if the primary
destination fails.
SDI 88 Path 2 Path 2 on SDI 88 is this group's
backup destination if the primary
destination fails.
SDI 88 Path 3 Path 3 on SDI 88 is this group's
backup destination if the primary
destination fails.
SDI 88 Path 4 Path 4 on SDI 88 is this group's
backup destination if the primary
destination fails.
SDI 92 Path 1 Path 1 on SDI 92 is this group's
backup destination if the primary
destination fails.
SDI 92 Path 2 Path 2 on SDI 92 is this group's
backup destination if the primary
destination fails.
SDI 92 Path 3 Path 3 on SDI 92 is this group's
backup destination if the primary
destination fails.
SDI 92 Path 4 Path 4 on SDI 92 is this group's
backup destination if the primary
destination fails.
To meet UL 864 requirements for
Central Station and Remote Station
applications, program a Backup
Device.
Select the communication device and the backup
destination. The backup device is used when the
primary device fails to reach the programmed
destination.
Refer to Section 5.5 Programming Path Numbers
and IP Addresses for Enhanced Communications on
page on page 131 to enable enhanced communication
paths.
Keypad Programming of R# Backup Device
D1255
1. Refer to Figure 1 on page 7 to access Keypad
Programming and navigate to the
ROUTE GRP 1 - 4 option.
2. At the ROUTE GRP 1 - 4 prompt, enter the route
group number you wish to configure and press
[ENT]. The keypad reads RT GRP 1 PRIMARY,
and then the current configuration (for example,
SDI 88 PATH 4).
3. Press [NEXT] to advance to the RT GRP 1
BACKUP option. The Primary device cannot be
set to No Device before setting the Backup
Destination.
4. To change the configuration, press [ENT] when
the current configuration shows, and then press
[NEXT] or [PREV] to scroll through the options, as
listed in R# Backup Device on page 20.
5. When the keypad reads the desired configuration
option, press [ENT] to select it.
When the keypad reads Parameter Saved, your
selection has been configured.
D1260
1. Refer to Figure 2 on page 8 to access Keypad
Programming and navigate to the
Route Group 1 - 4 option.
2. At the Route Group 1 - 4 prompt, enter the route
group number you wish to configure and press
[ENTER]. The keypad reads Rt Group 1 Primary,
and then the current configuration (for example,
SDI 88 PATH 4).
3. Press the Backup softkey. The keypad reads Rt
Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4). The
Primary device cannot be set to No Device before
setting the Backup Destination.
4. To change the configuration, press the Edit
softkey, and then press the Next or the Previous
softkey to scroll through the options, as listed in
R# Backup Device on page 20.
5. When the keypad reads the desired configuration
option, press the Save softkey to select it.
When the keypad reads Parameter Saved, your
selection has been configured.