3.4 COMMAND 7 and COMMAND 9
These entries assign point indexes, associated relays
that activate, and the text for the COMMAND 7 and
COMMAND 9 keypad functions.
CMD7 Point Index
Default: 31
Selection: 0 to 31
This entry selects one of the 31 P## Index codes that
define how the control panel reacts when a
COMMAND 7 is initiated.
The point index code used for
COMMAND 7 must not be used for any
other points on the system.
If the point index for COMMAND 7 has
Fire points programmed as Yes, this
causes access control doors to unlock if
Fire Unlock is also programmed as Yes.
Refer to the D9210B Program Entry
Guide (P/N: 32207).
CMD7 Relay
Default: 1
Selection: 0 to 8
This entry selects a relay (73 to 80 for the D9412GV3
or 9 to 16 for the D7412GV3) when COMMAND 7 is
initiated (refer to the
P### Relay
prompt on page
103 for relay number association).
COMMAND 7 does not activate the
Summary Fire Alarm relay.
CMD7 Point Text
Default: COMMAND 7
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters A to Z in capital letters
Enter up to sixteen characters of text to describe the
point. This point text appears at keypads (if the point
is programmed as visible) and sent to the D6500 or
D6600 when transmitting in Modem IIIa
2
format (if it is
a reporting point).
CMD9 Point Index
Default: 31
Selection: 0 to 31
This entry selects one of the 31 P## Index codes that
define how the control panel reacts when a
COMMAND 9 is initiated.
The point index code used for
COMMAND 7 and COMMAND 9 must not
be used for any other points on the
system.
If the point index for COMMAND 9 has
Fire points programmed as Yes, this
causes access control doors to unlock if
Fire Unlock is also programmed as Yes.
Refer to the D9210B Program Entry
Guide (P/N: 32207).
CMD9 Relay
Default: 1
Selection: 0 to 8
This entry selects a relay (73 to 80 on the D9412GV3
or 9 to 16 on the D7412GV3) when COMMAND 9 is
initiated (refer to the
P### Relay
prompt on page 103
for relay number association).
COMMAND 9 does not activate the
Summary Fire Alarm relay.
CMD9 Point Text
Default: COMMAND 9
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters (A to Z) in capital letters
Enter up to sixteen characters of text to describe the
point. This point text is displayed at keypads (if the
point is programmed as visible) and sent to the D6500
or D6600 when transmitting in Modem IIIa
2
format (if it
is a reporting point).