OUT T
- 54 -
{ OUT T ... Timer output
Usable device
Bit device
Word device
Con-
stant
Pointer Level
X Y M L SM F T C D R Z K H P N
Digit
desig-
nation
No. of
steps
Index
Device
Setting
value
3
Device No.(T0 to 255)
T0 D10
T0 K50
Setting value
(1 to 32767 is valid)
Setting value
(1 to 32767 is valid for
the data register details)
Device No.(T0 to 255)
Function
(1) When the operation results before the OUT command are ON, the timer coil will turn ON and
count to the set value. When the time is counted up (count value >= set value), the contacts will
change as shown below.
A contact Continuity
B contact Non-continuity
(2) If the operation results before the OUT command turn ON to OFF, the following will occur.
Before time up After time up
Timer type Timer coil
Timer current
value
A contact B contact A contact B contact
100ms timer
10ms timer
OFF
0
Non-
continuity
Continuity Continuity
Non-
continuity
100ms integrated
timer
OFF
Hold current
value
Non-
continuity
Continuity Continuity Non-
continuity
(3) The state of the integrated timer contact after time up will not change until the RST command is
executed.