Emerson MCU900 Video Game Controller User Manual


 
41
Reference Manual
IP2030/RM, Rev AA
Section 4: Getting started
June 2014
Section 4: Getting started
Using the App Wizard to set-up a flow application
Figure 4-15. App Wizard example: open channel flow with a 60° V-Notch Weir
App Wizard
Select Application
Esc=Back =Next
Flow
Options:
* Level
* Volume
* Flow
Flow Wizard
Select Output Units
gallons per min
Options
*
gallons per day
*
gallons per hour
*
gallons per min
*
Mega gals / day
*
Cubic ft per hour
*
Cubic ft per sec
Flow Wizard
Select Profile
V-Notch Weir (5/2)
Options
*
Flow Calculation
*
Flume/Weir (3/2)
*
V-Notch Weir (5/2)
*
V-Notch (ISO1438)
*
Vlarem
*
Parshall
*
Manning
*
20 point look-up
Enter max
flow
645.50 g/m
5
Enter height for
max flow
000001 ft
1
Enter flow
to give 4 mA out
000000 g/m
Enter flow
to give 20 mA out
645.50 g/m
6
Do you wish
to set up a
low flow cut off ?
(Wait while transferring plot points)
Choose method of
calibrating flow
HT for max flow
Options
*
Height for max flow
*
Flow at present height
Enter
low flow cut off
000001 %
2
Flow Wizard
complete
Totalizer Wizard
complete
Set up totalizer?
Display totalizer?
Set up Totalizer
relay?
Set up Sampler
relay?
Totalizer Wizard
Select Units
gallons x100
Options
*
gallons
*
gallons x10
*
gallons x100
*
gallons x1000
*
million gallons
*
cubic feet
Esc
Esc
Inhibit Totalizer
on digital input(s)?
Esc
0
APPLICATION DATA
INPUTS:
Level measurement in feet from transmitter.
Open channel is a 60° V-Notch Weir
Maximum flow is 645.50 gallons per minute.
Height at maximum flow is 1 ft.
OUTPUTS:
Flow rate in gallons per minute
Totalized flow in gallons x 100
2% low flow cut-off
x2
x2
x2
x5
(Edits 100.0 to be 645.5)
x4
x5
x5
x5
x5
x2
x2
(gallons per min)
(V-Notch Weir 5/2)
(Height for max flow)
(1)
(yes)
(2)
(0)
(645.50)
(continue)
(yes)
(gallons)
(yes)
(no)
(no)
(no)
(continue)
Exits to menu system.
(Select Run App mode
to start application).
x2