Reference Manual
IP2030/RM, Rev AA
Section 4: Getting started
June 2014
Section 4: Getting started40
Using the App Wizard to set-up a contents volume application
Figure 4-14. App Wizard example: tank volume with a high alarm
App Wizard
Select Application
Esc=Back =Next
Volume
Options:
* Level
* Volume
* Flow
Volume Wizard
Select Tank Shape
Horiz cyl flat
Options
* Vertical cylinder
* Horiz Cyl flat
* Horiz Cyl domed
* Rectangular
* Spherical
* Conical bottom
* 20 point table
(Wait while transferring plot points)
Choose method of
calibrating Tank
Tank dimensions
Options
*
Tank dimensions
*
Maximum volume
Enter value
of Tank diameter
6.5000 ft
5
Enter value
of Tank Length
255000 ft
.
Volume Wizard
max Tank Volume
6205.6 gal
Set Current Output ?
Enter volume
to give 4 mA out
000000 gal
Enter volume
to give 20 mA out
6200.0 gal
0
Set up Relays ?
Relay Wizard
Select Function
Relay(s)
Options
*
Relay(s)
*
Pump Control
*
Custom
Options
*
Relay 1
*
Relay 2
*
Relay 3
*
Relay 4
Select Mode for
Relay 1
Hi or Lo Alarm
Options
*
*
Rate of change
Relay(s)
Select Relay
Relay 1
*
Out of limits
*
Digital input
*
Hi or Lo Alarm
Enter On point
for Relay 1
006000 gal
Enter Off point
for Relay 1
005800 gal
8
6
Set point
Setup Complete
Program further
Relays?
Esc
0
APPLICATION DATA
INPUTS:
Level measurement in feet from transmitter.
Transmitter Bottom Reference is 7.5 ft.
Tank is a horizontal cylinder with flat ends.
Tank dimensions are 6.5 ft. dia. x 25 ft. length.
Volume capacity is 6205.6 gallons.
OUTPUTS:
Contents volume in US gallons displayed.
Relay on at 6000 gallons; off at 5800 gallons.
Current Output range 0 to 6200 gallons.
x6
x5
x2
x5
x5
x6
x6
x5
x8
x2
x2
x3
(Horiz
cyl flat)
(Tank
dimensions)
(continue)
(6.5)
(25.0)
(yes)
(0)
(Edits 6205.6 to be 6200.0)
(yes)
(Relays)
(Hi or Lo Alarm)
(6000)
(5800)
(no)
Exits to menu system.
(Select Run App mode
to start application).
(Relay 1)
x2