Reference Manual
IP2030/RM, Rev AA
Appendix D: Additional Features
June 2014
135
Appendix D: Additional Features
Appendix D Additional Features
Restoring the factory defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 135
ADVANCED parameter access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 136
D.1 Restoring the factory defaults
D.1.1 How to restore the factory default settings
Note
The factory defaults may not be the same as the settings when shipped from the
factory. It is advisable to keep a record of settings, if possible.
Procedure to restore the control unit to the factory defaults,
erasing all user-entered data
1. If there are HART transmitters connected:
a. Navigate to SETUP / [CONTROLLER /] SYSTEM / Transmitter Wizard
b. Start the Wizard, and use the Remove option for each connected transmitter.
This removal action clears the control unit memory of all transmitter data that has been
uploaded from a HART transmitter, including the Transmitter Bottom Reference.
2. Navigate to the SETUP / [CONTROLLER /] SYSTEM / DEFAULTS menu (see Figure 8).
3. Press the red (ENTER) button twice and then wait until “Done”.
4. Switch off
5. If there are two transmitters connected to a Mobrey MCU902 control unit:
a. Switch-off power to the MCU900 Series control unit.
b. Remove the second transmitter that is associated with Transmitter Input Channel 2.
c. Switch-on power to the MCU900 Series control unit
6. Put the control unit into Run App mode (to automatically find a HART transmitter)
7. If the control unit is a Mobrey MCU902 control unit:
a. Switch-off power to the MCU900 Series control unit.
b. Re-connect the second transmitter.
c. Switch-on power to the MCU900 Series control unit
8. Turn back to Section 4: Getting started, to start again.