Emerson MCU900 Video Game Controller User Manual


 
39
Reference Manual
IP2030/RM, Rev AA
Section 4: Getting started
June 2014
Section 4: Getting started
4.5.4 Application Wizard
Use the Application Wizard (App Wizard) to easily set-up the control unit for an application.
If a message appears saying that the units are not set, it is because the HART transmitter has not
been found by the control unit when power was applied. Change the operating mode from
Program to Run App mode and the control unit will attempt to re-connect to the transmitter.
Note
When using a MCU902 control unit, it is necessary to select Difference, Sum, Product,
or Independent (and channel) before Level/Volume/Flow can be selected.
Level and volume measurement duties are not available on the MCU90F Logging unit.
Using the App Wizard to set-up a level application
Figure 4-13. App Wizard example: pump control with a high alarm
App Wizard
Select Application
Esc=Back =Next
Level
Options:
* Level
* Volume
* Flow
Set Current Output ?
Set up Relays ?
Relay Wizard
Select Function
Pump Control
Options
*
Relay(s)
*
Pump Control
*
Custom
Select Mode for
Relay 3
Hi or Lo Alarm
Options
*
*
Rate of change
*
Out of limits
*
Digital input
Enter On point
for Relay 3
000012 ft
Enter Off point
for Relay 3
000011 ft
1
2
Set point
*
Hi or Lo Alarm
Setup Complete
Program further
Relays?
Pump Control
Number of Pumps
2
Options
*
Assist com off
*
Assist split off
*
Stby com off
*
Stby split off
Select Pump Control
Duty
Assist com off
Number of starts
Qualifier
00
4
Options
*
Number of starts
*
Run-Time
*
Ratio of Run-Time
*
Ratio of starts
Select
Autosequence on
t
Number of starts
Enter On point
for Pump 1
000000 ft
5
Enter On point
for Pump 2
000000 ft
8
Lowest common
off point
000000 ft
1
Pump Control
Select
Autosequence Mode ?
Relay Wizard
Select Function
Relay(s)
Relay(s)
Select Relay
Relay 3
Options
*
Relay(s)
*
Pump Control
*
Custom
Setup Complete
Program further
Relays?
Esc
Esc
APPLICATION DATA
INPUTS:
Level measurement in feet from transmitter.
Transmitter Bottom Reference is 22 ft.
Sump/lift station working level is 20 ft.
2-pump operation required is duty assist with
common off. Auto-sequencing after 4 starts.
OUTPUTS:
Level in feet.
Relay 1 (Pump 1) on at 5 ft.; off at 1 ft.
Relay 2 (Pump 2) on at 8 ft.; off at 1 ft.
Relay 3 (High Alarm) on at 12 ft.; off at 11 ft.
x5
x8
x4
x5
x5
x5
x4
x4
x2
(no)
(yes)
(Pump
control)
(2)
(Assist
com off)
(5)
(5)
(1)
(yes)
(Number
of starts)
(4)
(yes)
A
A
(Relays)
(Relay 3)
(Hi or Lo
Alarm)
(12)
(11)
(no)
x2
Exits to menu system.
(Select Run App mode to start application).