Hitachi NJI-350B Video Game Controller User Manual


 
Chapter 12 Error Code List and Special Internal Outputs
12-4
12.3 Operation Error Codes
If an error occurs when a control instruction is executed, “1” is set in the operation error (ERR) special internal output
“R7F3” and an error code (hexadecimal) indicating the description of the error is set in WRF015.
To clear the operation errors to zeros, execute “R7F3=0” using a forced setting from a program or peripheral unit. To
clear the error codes to zeros, execute “WRF015=0” using a forced setting from a program or peripheral unit.
Error code Error name Description of error
Originating
instruction
H0013 SB undefined SBn instruction corresponding to the instruction
number n in the CALn instruction is not
programmed
CAL
H0015 LBL undefined LBLn instruction corresponding to the instruction
number n in the JMPn and CJMPn instructions is
not programmed
JMP
CJMP
H0016 FOR undefined FORn instruction corresponding to the instruction
number n in the NEXTn instruction is not
programmed
NEXT
H0017 NEXT undefined NEXTn instruction corresponding to the
instruction number n in the FORn instruction is
not programmed
FOR
H0040 LBL area error LBLn instruction corresponding to the instruction
number n in the JMPn and CJMPn instructions is
not programmed in the same program area
JMP
CJMP
H0041 CAL nesting overflow There are more than 6 levels of subroutine nesting CAL
H0042 CAL undefined RTS instruction was executed without executing
the CAL instruction
RTS
H0043 FOR to NEXT error There is a NEXTn with the same instruction
number n prior to the FORn instruction
FOR
H0044 NEXT area error There is no NEXTn instruction with the same
instruction number n as the FORn instruction in
the same program area
FOR
H0045 FOR to NEXT nesting
overflow
The FORn and NEXTn instructions are not nested FOR
H0046 FOR nesting overflow There are more than 6 nesting levels of FOR to
NEXT
FOR
NEXT