EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958198
CoolOccSpt nciTempSetPts
(SNVT_temp_setpt)
occupied_cool Degrees F
50 to 95
Degrees C
(10 to 35)
23 P,
M
X X The Cooling Occupied Setpoint is used if no wall module setpoint pot is
configured as the standard Occupied Cooling Setpoint. Actual Cooling
Setpoint can be affected by various control parameters (such as DlcShed,
SrcRmtTempSpt, etc.). Actual room temperature Setpoint is reflected in
RmTempActSpt. Overridden by nviSetPt. Used to compute ZEB.
CoolStbySpt nciTempSetPts
(SNVT_temp_setpt)
standby_cool Degrees F
50 to 95
Degrees C
(10 to 35)
25 P,
M
X X When the controller is in the Standby mode (typically via an occupancy
sensor), the base Cooling Setpoint is determined by the Cooling Standby
Setpoint value. Also, when a wall module setpoint pot is configured, this
value serves as the upper limit on the user adjustable remote setpoint pot
(wall module).
CoolUnoccSpt nciTempSetPts
(SNVT_temp_setpt)
unoccupied_cool Degrees F
50 to 95
Degrees C
(10 to 35)
28 P,
M
X X When the controller is in the Unoccupied mode, the unit responds to a call
for cooling based on the Cooling Unoccupied Setpoint.
HeatOccSpt nciTempSetPts
(SNVT_temp_setpt)
occupied_heat Degrees F
50 to 95
Degrees C
(10 to 35)
21 P,
M
X X When the controller is in the Occupied mode, if the space temperature
drops below the Heating Occupied Setpoint, the unit switches to the
Heating mode. This Setpoint is used only when there is no wall module
setpoint pot configured. Overridden by nviSetPt. Used to compute ZEB.
HeatStbySpt nciTempSetPts
(SNVT_temp_setpt)
standby_heat Degrees F
50 to 95
Degrees C
(10 to 35)
19 P,
M
X X When the controller is in the Standby mode (typically via an occupancy
sensor), the base Heating Setpoint is determined by the Heating Standby
Setpoint value. Also, when a wall module setpoint pot is configured, this
value serves as the lower limit on the user adjustable remote setpoint pot
(wall module).
HeatUnoccSpt nciTempSetPts
(SNVT_temp_setpt)
unoccupied_heat Degrees F
50 to 95
Degrees C
(10 to 35)
16 P,
M
X X When the controller is in the Unoccupied mode, the unit responds to a call
for heating based on the Heating Unoccupied Setpoint.
nviRequest
(SNVT_obj_request)
object_id 0 to 65535 1 Request provides the mechanism to request a particular status report (via
Status) for a particular object within this node. Object_id selects the object
being referenced by nviRequest. The only valid value of object_id is 1 for
the RTU object and all others are invalid.
nviRequest
(SNVT_obj_request)
object_request RQ_NORMAL
RQ_DISABLED
RQ_UPDATE_STATUS
RQ_SELF_TEST
RQ_UPDATE_ALARM
RQ_REPORT_MASK
RQ_OVERRIDE
RQ_ENABLE
RQ_RMV_OVERRIDE
RQ_CLEAR_STATUS
RQ_CLEAR_ALARM
RQ_NUL
0
1
2
3
4
5
6
7
8
9
10
255
RQ_NORMAL When object_request is RQ_NORMAL or RQ_UPDATE_STATUS then the
status (via Status) will be reported for the object addressed by object_id.
When object_request is RQ_REPORT_MASK then the status bits will be
reported that are supported in nvoStatus by the object addressed by
object_id. Bits that are supported by the object are set to one. All other
object_request items are not supported at this time and will return an
invalid_request (Status) in the object status.
Table 26. L
ON
M
ARK
®/Open System Points. (Continued)
User Address NvName Field Name
Engineering Units: English
(Metric) or States plus Range
Digital State or
Value of State
Default
E-Vision (M, P, S)
Share
Map
Direct Access
Hardware Config.
Manual Config.
Failure Detect
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments