EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
103 74-2958—1
nvoStatus
(SNVT_obj_request)
electrical_fault FALSE
TRUE
0
1
FALSE The electrical_fault field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
unable_to_measure FALSE
TRUE
0
1
FALSE The unable_to_measure field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
comm_failure FALSE
TRUE
0
1
FALSE The comm_failure field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
fail_self_test FALSE
TRUE
0
1
FALSE The fail_self_test field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
self_test_in_progress FALSE
TRUE
0
1
FALSE The self_test_in_progress field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
locked_out FALSE
TRUE
0
1
FALSE The locked_out field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
manual_control FALSE
TRUE
0
1
FALSE The manual_control field is not supported and is set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
in_alarm FALSE
TRUE
0
1
FALSE If there are currently any active alarms reported by SrcUnitStatus.in_alarm
or SrcUnitStatus.in_alarm is set to ALARM_NOTIFY_DISABLED,in_alarm
is set to 1 (TRUE), otherwise in_alarm is set to 0 (FALSE). When
Request.object_request is RQ_REPORT_MASK, then disabled and
in_alarm are set to 1 (TRUE) to indicate that these functions are supported
while all other fields are set to 0 (FALSE).
nvoStatus
(SNVT_obj_request)
in_override FALSE
TRUE
0
1
FALSE The in_override field is not supported and is set to 0 (FALSE).
DestOccSensor nviSensorOcc
(SNVT_occupancy)
OC_OCCUPIED
OC_UNOCCUPIED
OC_BYPASS
OC_STANDBY
OC_NUL
0
1
2
3
255
OC_NUL M X X X X nviSensorOcc allows an occupancy sensor at another node to be used as
the occupancy sensor for this node and is typically bound to SensorOcc of
another node. The nviSensorOcc input must show OC_UNOCCUPIED for
300 seconds before it is used by the controller for triggering UN_OC
operation. This makes it possible for several occupancy sensors to be
ORed together by binding them all to nviSensorOcc. If any one bound
occupancy sensor shows occupancy, then SensorOcc shows occupancy
for up to 300 seconds after the last sensor shows OC_OCCUPIED. The
valid states have the following meanings: OC_OCCUPIED indicates
occupied. OC_BYPASS, OC_STANDBY, and all unspecified values
indicates the same as OC_OCCUPIED. OC_UNOCCUPIED or OC_NUL
indicates not occupied.
SrcOccSensor nvoSensorOcc
(SNVT_occupancy)
OC_OCCUPIED
OC_UNOCCUPIED
OC_BYPASS
OC_STANDBY
OC_NUL
0
1
2
3
255
OC_NUL M X X nvoSensorOcc is an output showing the current state of the hard wired
occupancy sensor. The valid states are as follows: OC_OCCUPIED
indicates that the space is occupied. OC_UNOCCUPIED indicates that the
space is not occupied. OC_NUL means no output is available because it is
not configured.
Table 26. L
ON
M
ARK
®/Open System Points. (Continued)
User Address NvName Field Name
Engineering Units: English
(Metric) or States plus Range
Digital State or
Value of State
Default
E-Vision (M, P, S)
Share
Map
Direct Access
Hardware Config.
Manual Config.
Failure Detect
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments