EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
69 74-29581
nciIoSelect DigitalOut[0] COOL_STAGE_1
COOL_STAGE_2
COOL_STAGE_3
COOL_STAGE_4
HEAT_STAGE_1
HEAT_STAGE_2
HEAT_STAGE_3
HEAT_STAGE_4
CHANGE_OVER_RELAY
FAN_OUT
AUX_ECON
OCCUPANCY_STATUS
ECON_OPEN
ECON_CLOSE
COOL_OPEN
COOL_CLOSE
HEAT_OPEN
HEAT_CLOSE
HEAT_COOL_STAGE_1
HEAT_COOL_STAGE_2
HEAT_COOL_STAGE_3
HEAT_COOL_STAGE_4
FREE1
FREE2
FREE1_PULSE_ON
FREE1_PULSE_OFF
ECON_PWM
HEAT_PWM
COOL_PWM
UNUSED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
25
26
27
28
29
30
31
255
NETWORK DO(FREE1)
(Value of State is 25)
X DigitalOut[0] specifies which logical digital output function is assigned to the
digital physical output according to the enumerated list that is shown in the
Engineering Units/States column. The W7750 Controllers are configured at
the factory with the enumerated value in the Default column. Only
DigitalOut[0] through DigitalOut[5] are available in the W7750A model
which can configure staged outputs. The W7750A Controller can drive
Series 60 Floating Control to modulate cooling valves, heating valves and
economizers. (No PWM outputs are allowed in the W7750A model.) The
controller is configured at the factory with the enumerated value in the
Default column. The eight outputs on the W7750B are all digital outputs.
The eight outputs on the W7750C consist of five digital and three analog
outputs.
nciIoSelect DigitalOut[1] See DigitalOut[0] enumerated
values
1-31
,255
FAN_OUT
(Value of State is 10)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[2] See DigitalOut[0] enumerated
values
1-31
,255
COOL_STAGE_2
(Value of State is 2)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[3] See DigitalOut[0] enumerated
values
1-31
,255
HEAT_STAGE_1
(Value of State is 1)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[4] See DigitalOut[0] enumerated
values
1-31
,255
HEAT_STAGE_2
(Value of State is 3)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[5] See DigitalOut[0] enumerated
values
1-31
,255
HEAT_STAGE_1
(Value of State is 5)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[6] See DigitalOut[0] enumerated
values
1-31
,255
UNUSED
(Value of State is 255)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect DigitalOut[7] See DigitalOut[0] enumerated
values
1-31
,255
UNUSED
(Value of State is 255)
X See DigitalOut[0] for enumerated names. The W7750 Controllers are
configured at the factory with the enumerated value in the Default column.
nciIoSelect HtPump CONV
HP
0
1
CONV P X HtPump specifies the type of equipment being controlled. When HtPump is
0 (CONV), the node is controlling conventional gas or electric heat. When
HtPump is 1 (HP), the node is controlling a heat pump.
Table 20. Input/Output Points. (Continued)
User Address NvName Field Name
Engineering Units: English
(Metric) or States plus Range
Digital State or
Value of State
Default
E-Vision (M, P, S)
Share
Map
Direct Access
Hardware Config.
Manual Config.
Test
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments