EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
91 74-2958—1
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 0
(RtnEnthalpyError)
FALSE
TRUE
0
1
FALSE RtnEnthalpyError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 1
(MonitorSensorError)
FALSE
TRUE
0
1
FALSE MonitorSensorError: All control functions associated with the failed sensor
are disabled as if the sensor was not configured.
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 2
(SpaceCO2Error)
FALSE
TRUE
0
1
FALSE SpaceCO2Error: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 3
(FilterStaticPresError)
FALSE
TRUE
0
1
FALSE FilterStaticPresError: All control functions associated with the failed sensor
are disabled as if the sensor was not configured.
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 4
(ADCalError)
FALSE
TRUE
0
1
FALSE ADCalError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[1]
Byte Offset = 1
Bit Offset = 7
(nvApplModeError)
FALSE
TRUE
0
1
FALSE ApplModeError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
nvoError error_bit[2]
Byte Offset = 2
Bit Offset = 0
(nvSetPtOffsetError)
FALSE
TRUE
0
1
FALSE SetPtOffsetError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
nvoError error_bit[2]
Byte Offset = 2
Bit Offset = 1
(nvSpaceTempError)
FALSE
TRUE
0
1
FALSE SpaceTempError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
nvoError error_bit[2]
Byte Offset = 2
Bit Offset = 2
(nvOdTempError)
FALSE
TRUE
0
1
FALSE OdTempError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
nvoError error_bit[2]
Byte Offset = 2
Bit Offset = 3
(nvOdHumError)
FALSE
TRUE
0
1
FALSE OdHumError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
nvoError error_bit[2]
Byte Offset = 2
Bit Offset = 4
(nvSensorOccError)
FALSE
TRUE
0
1
FALSE SensorOccError: All control functions associated with the failed NV are
disabled as if the NV was not configured.
Table 23. Status Points. (Continued)
User Address NvName Field Name
Engineering Units: English
(Metric) or States plus Range
Digital State or
Value of State
Default
E-Vision (M, P, S)
Share
Map
Direct Access
Hardware Config.
Manual Config.
Test
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments