EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958190
MonitorSens nvoCtlDataG2 siMonitor1S10 volts
1 to 10
SI_INVALID X siMonitor1S10: siMonitor1S10 is the voltage applied at the monitor input
terminals. If the sensor is not configured or has failed, the value is
SI_INVALID.
CoolPos nvoCtlDataG2 sbCoolPosS0 Percentage
0 to 100
0 X sbCoolPosS0: If the node is configured for modulating cool, sbCoolPosS0
shows the current position of the cooling modulating output.
HeatPos nvoCtlDataG2 sbHeatPosS0 Percentage
0 to 100
0 X sbHeatPosS0: If the node is configured for modulating heat, sbHeatPosS0
shows the current position of the heating modulating output.
EconPos nvoCtlDataG2 sbEconPosS0 Percentage
0 to 100
0 X sbEconPosS0: If the node is configured for modulating economizer,
sbEconPosS0 shows the current position of the economizer modulating
output.
StatusError nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 0
(SpaceTempError)
FALSE
TRUE
0
1
FALSE X For SpaceTempError, a value of 1 (TRUE) indicates that data was not
available from the sensor and will result in a SENSOR_FAILURE alarm. A
value of 0 (FALSE) indicates a normal condition. The heating and cooling
control loops will be turned off it there is a space temp sensor failure. The
fan will remain under normal control.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 1
(SetPtError)
FALSE
TRUE
0
1
FALSE For SetPtError, see preceding. Upon a failure of the local setpoint, the
control loop will use the default occupied setpoints to control space
temperature.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 2
(OdTempError)
FALSE
TRUE
0
1
FALSE For OdTempError, see preceding. All control functions associated with the
failed sensor are disabled as if the sensor was not configured.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 3
(OdHumError)
FALSE
TRUE
0
1
FALSE For OdHumError, see preceding. A value of 0 (FALSE) indicates a normal
condition. All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 4
(OdEnthalpyError)
FALSE
TRUE
0
1
FALSE OdEnthalpyError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 5
(DischgTempError)
FALSE
TRUE
0
1
FALSE DischgTempError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 6
RtnTempError)
FALSE
TRUE
0
1
FALSE RtnTempError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
nvoError error_bit[0]
Byte Offset = 0
Bit Offset = 7
(RtnHumError)
FALSE
TRUE
0
1
FALSE RtnHumError: All control functions associated with the failed sensor are
disabled as if the sensor was not configured.
Table 23. Status Points. (Continued)
User Address NvName Field Name
Engineering Units: English
(Metric) or States plus Range
Digital State or
Value of State
Default
E-Vision (M, P, S)
Share
Map
Direct Access
Hardware Config.
Manual Config.
Test
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments