Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
92
T1/T1S User’s Manual
6. Programming Information
6.1 Devices and registers
The T1/T1S program consists of bit-based instructions that handle ON/OFF information,
such as contact and coil instructions, and register-based (16-bit) instructions, such as
those for data transfer and arithmetic operations.
Devices are used to store the ON/OFF information of contacts and coils, and registers
are used to store 16-bit data.
Devices are divided into six types:
X External input devices
Y External output devices
R Auxiliary relay devices
S Special devices
T. Timer devices
C. Counter devices
Registers are divided into eight types:
XW External input registers
YW External output registers
RW Auxiliary relay registers
SW Special registers
T Timer registers
C Counter registers
D Data registers
I, J, K Index registers
Device and register numbers
X devices share the same memory area as XW registers. Device X014, for example,
represents the number 4 bit in the XW01 register.
Bit position / Number
(MSB) (LSB)
FEDCBA9876543210
XW01 1
X014
Thus, "X014 is ON" means that bit number 4 of XW01 is 1.
Y, R, and S devices work in a similar manner.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net