6F3B0250
78
T1/T1S User’s Manual
4. Installation and Wiring
4.5 Power supply wiring
Wire the power source to the T1/T1S power supply terminals.
·
Power conditions:
AC power supply type DC power supply type
Rated voltage 100 to 240 Vac, +10/-15 % 24 Vdc, +20/-15 %
Frequency
50/60 Hz,
±
5 %
-
Power consumption 30 VA or less (T1-16/T1-28)
38 VA or less (T1-40)
45 VA or less (T1-40S)
12 W or less (T1-16/T1-28)
18 W or less (T1-40)
18 W or less (T1-40S)
Retentive power
interruption
Continuous operation for less than 10 ms
·
1.25 mm
2
(16 AWG) twisted-pair cable should be used for the power cable.
·
The power cable should be separated from other cables.
!
CAUTION
1. Turn off power before wiring to minimize the risk of electrical shock.
2. Applying excess power voltage to the T1/T1S can cause explosion or fire.
Apply power of the specified ratings described below.
Insulation
transformer
Line filter
Power source
T1
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net