Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
68
T1/T1S User’s Manual
4. Installation and Wiring
4.1 Environmental conditions
Do not install the T1/T1S in the following locations:
·
Where the ambient temperature drops below 0
°
C or exceeds 55
°
C.
·
Where the relative humidity drops below 20 % or exceeds 90 %.
·
Where there is condensation due to sudden temperature changes.
·
In locations subject to vibration that exceeds tolerance.
·
In locations subject to shock that exceeds tolerance.
·
Where there are corrosive or flammable gases.
·
In locations subject to dust, machining debris or other particles.
·
In locations exposed to direct sunlight.
Observe the following precautions when installing enclosures in which the T1/T1S will be
installed:
·
Provide the maximum possible distance from high-voltage or high-power panels. This
distance must be at least 200 mm.
·
If installing the enclosures in the vicinity of high-frequency equipment, be sure to
correctly ground the enclosures.
·
When sharing the channel base with other panels, check for leakage current from the
other panels or equipment.
!
CAUTION
Excess temperature, humidity, vibration, shocks, or dusty and corrosive gas
environment can cause electrical shock, fire or malfunction.
Install and use the T1/T1S and related equipment in the environment
described in this section.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net