7. Instructions
FUN 063 ATOH ASCII to Hex conversion
Expression
Input
-
[
A
ATOH (
n
)
B
]
-
Output
Function
When the input is ON, the ASCII characters stored in
n
registers starting with
A
is converted into
hexadecimal data and stored in
B
and after. The lower byte of source
A
is stored as uppermost digit of
destination
B
, and followed in this order. The allowable ASCII character in the source table is “0” (H30)
to “9” (H39) and “A” (H41) to “F” (H46). The allowable range of
n
is 1 to 64.
Execution condition
Input Operation Output ERF
OFF No execution OFF
-
ON Normal execution ON
-
Conversion data error (no execution) OFF Set
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Source
ÖÖÖÖÖÖÖÖÖÖ Ö
n
Data size 1 - 64
B
Destination
ÖÖÖÖÖÖ
Example
When R011 is ON, the ASCII characters stored in 8 words of D0300 to D0307 are converted into
hexadecimal data, and stored in 4 words registers starting with RW040.
F870 F 0
D0300 “1” (H31) “0” (H30) RW040 H0123
D0301 “3” (H33) “2” (H32) Converted RW041 H4567
D0302 “5” (H35) “4” (H34) RW042 H89AB
D0303 “7” (H37) “6” (H36) RW043 HCDEF
D0304 “9” (H39) “8” (H38)
D0305 “B” (H42) “A” (H41)
D0306 “D” (H44) “C” (H43)
D0307 “F” (H46) “E” (H45)
Note
·
If index register (I, J or K) is used for the operand
A
, only
n
= 1 is allowed.
·
If
n
is odd number, lower 2 digits of the last converted data will not be fixed, Use even for
n
.
T1S only