Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
158
T1/T1S User’s Manual
7. Instructions
FUN 024 TINZ Table initialize
Expression
Input
-
[
A
TINZ (
n
)
B
]
-
Output
Function
When the input is ON, the data of
A
is stored in
n
registers starting with
B
.
The allowable range of the table size
n
is 1 to 1024 words.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution ON
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Source
ÖÖÖÖÖÖÖÖÖÖ Ö
n
Table size 1 - 1024
B
Start of
destination
ÖÖÖÖÖÖ
Example
When R010 is ON, a constant data (0) is stored in 100 registers starting with D0200 (D0200 to
D0299) and the output is turned ON.
Constant 0 D0200 0
D0201 0
D0202 0 100 registers
D0299 0
T1S only