Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
Basic Hardware and Function
197
7. Instructions
FUN 097
>=
Greater than or equal
Expression
Input
-
[
A
>=
B
]
-
Output
Function
When the input is ON, the data of
A
and the data of
B
are compared, and if
A
is greater than or equal
to
B
, the output is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A
³
B
ON
A
<
B
OFF
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Compared
data
ÖÖÖÖÖÖÖÖÖÖ Ö Ö
B
Reference data
ÖÖÖÖÖÖÖÖÖÖ Ö Ö
Example
When R00C is ON, the data of D0125 is compared with the data of D0020, and if the data of
D0125 is greater than or equal to the data of D0020, R020 is turned ON.
If the data of D0125 is 3000 and that of D0020 is 3000, the comparison result is true.
Consequently, R020 is turned ON.
D0125 3000
³
D0020 3000 R020 is ON
If the data of D0125 is -1500 and that of D0020 is 0, the comparison result is false. Consequently,
R020 is turned OFF.
D0125 -1500
<
D0020 0 R020 is OFF
Note
·
This instruction deals with the data as signed integer (-32768 to 32767).
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net