D
>
Double-word greater than
Expression
Input
-
[
A+1
×
A
D
>
B+1
×
B
]
-
Output
Function
When the input is ON, the double-word data of
A+1
×
A
and
B+1
×
B
are compared, and if
A+1
×
A
is greater
than
B+1
×
B
, the output is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A+1
×
A
>
B+1
×
B
ON
A+1
×
A
£
B+1
×
B
OFF
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Compared
data
ÖÖÖÖÖÖÖ Ö
B
Reference data
ÖÖÖÖÖÖÖ Ö
Example
When R010 is ON, the data of D0101
×
D0100 is compared with the constant data 200000, and if
the data of D0101
×
D0100 is greater than 200000, R014 is turned ON.
If the data of D0101
×
D0100 is 250000, the comparison result is true. Consequently, R014 is
turned ON.
D0101
×
D0100 250000
>
Constant 200000 R014 is ON
If the data of D0101
×
D0100 is -100, the comparison result is false. Consequently, R014 is turned
OFF.
D0101
×
D0100 -100
£
Constant 200000 R014 is OFF
Note
·
This instruction deals with the data as double-word integer (-2147483648 to 2147483647).