Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
152
T1/T1S User’s Manual
7. Instructions
JCS
JCR
Jump control set / reset
Expression
Input [ JCS ]
[ JCR ]
Function
When the JCS input is ON, instructions between JCS and JCR are skipped (not executed). When the
JCS input is OFF, ordinary operation is performed.
Execution condition
JCS
input
Operation Output
OFF Ordinary operation
ON Skips until JCR
Operand
No operand is required.
Example
When X000 is ON, the rung 2 circuit is skipped, therefore Y021 is not changed its state regardless
of the X001 state. When X000 is OFF, Y021 is controlled by the X001 state.
Note
·
JCS and JCR must be used as a pair.
·
Nesting is not allowed.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net