Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
Basic Hardware and Function
147
7. Instructions
TON ON delay timer
Expression
Input
¾
[
A
TON
B
]
¾
Output
Function
When the input is changed from OFF to ON, timer updating for the timer register
B
is started. The
elapsed time is stored in
B
. When the specified time by
A
has elapsed after the input came ON, the
output and the timer device corresponding to
B
are turned ON. (Timer updating is stopped)
When the input is changed from ON to OFF,
B
is cleared to 0, and the output and the timer device are
turned OFF.
The available data range for operand
A
is 0 to 32767.
Execution condition
Input Operation Output
OFF No operation (timer is not updatin
g
)OFF
ON
Elapsed time
<
preset time (timer is updatin
g
)
OFF
Elapsed time
³
preset time (timer is not updatin
g
)
ON
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Preset time
ÖÖÖÖÖÖÖÖÖÖ
0 - 32767
B
Elapsed time
Ö
Example
Y021 (and the timer device T.000) is turned ON 2 seconds after X000 came ON.
X000
T000
T.000
Y021
Preset time (2s) Less than preset time
Preset value
Note
·
Time is set in 10 ms units for;
T1: T000 to T031 (0 to 327.67 s)
T1S: T000 to T063 (0 to 327.67 s)
·
Time is set in 100 ms units for;
T1: T032 to T063 (0 to 3276.7 s)
T1S: T064 to T255 (0 to 3276.7 s)
·
Multiple timer instructions (TON, TOF or
SS) with the same timer register are not
allowed.