Toshiba 6F3B0250 Video Gaming Accessories User Manual


 
6F3B0250
146
T1/T1S User’s Manual
7. Instructions
( N )
Negative pulse coil
Expression
A
Input (
N
)
Function
When the input is changed form ON to OFF, the device
A
is set to ON for 1 scan time.
This instruction is used to detect the input changing from ON to OFF.
Execution condition
Input Operation Output
OFF When the input at last scan is OFF, sets
A
to OFF
-
When the input at last scan is ON, sets
A
to ON
-
ON Sets device
A
to OFF
-
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Device
ÖÖÖ
Example
R101 comes ON for only 1 scan when X000 is changed from ON to OFF.
X000
R100
1 scan time 1 scan time
Note
·
The maximum usable number in a program is 2048.
(
P N (P) (N)
total)
T1S only