T1/T1S User’s Manual
7. Instructions
FUN 146 STOT Step sequence output
Expression
Input
-
[ STOT
A
]
Function
When the input is ON, the device
A
is set to ON and the devices of STIN instructions on the same rung
are reset to OFF.
Execution condition
Input Operation Output
OFF No execution
-
ON Execution
-
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Step device
Ö
Example
See example on STIN (FUN 145) instruction.
Note
·
The STIZ, STIN and STOT instructions are used together to configure the step sequence.
·
Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.
·
Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop or
convergence of sequences. (Max. 11 STIN instructions on one rung)
·
To perform the conditional branch (sequence selection), separate the rungs as follows.
This limitation is applied to T1 version 1.00 only.
[ STIN
A
] | | [ STOT
B
] [ STIN
A
] | | [ STOT
B
]
| | [ STOT
C
] [ STIN
A
] | | [ STOT
C
]
Not allowed Available