The operating mode of the CPM2B when the power is turned ON depends upon
the PC Setup setting in DM 6600 and the Programming Consoles mode switch
setting if the Programming Console is connected.
PC Setup setting
(DM 6600)
Programming
Console connected
Programming Console not
connected
00xx The startup mode
determined by the
mode switch setting.
RUN mode if no Programming Device
is connected. PROGRAM mode if
another Programming Device is
connected.
01xx The startup mode is the same as the operating mode before
power was interrupted.
0200 PROGRAM mode
0201 MONITOR mode
0202 RUN mode
Note The default setting is 00xx. With this default setting, the PC will automatically
enter RUN mode if a Programming Console is not connected and SW201 is ON.
Be sure that it is safe for the PC to operate before turning it ON under these
conditions.
6-1-3 Connecting the Programming Console
Connect the Programming Consoles connecting cable to the CPM2Bs periph-
eral port, as shown below.
Peripheral port
CPM2C-CN111
Connecting Cable
(0.1 m) (See note 2.)
CS1W-CN114
Connecting Cable
(0.05 m)
CQM1-PRO01-E
CS1W-CN224 (2 m) or
CS1W-CN624 (4 m)
Connecting Cable
CPM2B CPU Board
C200H-PRO27-E
C200H-CN222 (2 m) or
C200H-CN422 (4 m)
Connecting Cable
Attached
cable (2 m)
Peripheral port
connector
SW201
(See note 1.)
Note 1. Always turn OFF SW 201 before connecting the Programming Console.
2. Only the peripheral port connector can be used when a CPM2C-CN111
Connecting Cable is connected.
Startup Operating Mode