Sierra S5832SG Video Game Controller User Manual


 
1
S5832SG Terminal Layout
Introduction
This manual contains basic information and program-
ming information for the Sierra Model S5832SG con-
trol panel.
For additional information regarding programming and
applications, refer to the Expanded Programming sec-
tion of the S5090 Sierra Reference Manual.
Mounting the Panel
The Sierra S5832SG should be mounted in a location
which allows convenient access to AC power, tele-
phone connections, and earth ground (see Figure 2).
Remove the knock-outs, if necessary.
Mark the screw mounting holes on the wall, using
the cabinet as a template.
Mount the cabinet at the desired height and pass
the cables through the knock-outs.
Mount the circuit board to the stand-offs. The stand-
offs are factory installed. The metal stand-off (lower
left corner) has a panhead screw to be used for con-
necting earth ground.
Connect the earth ground wire (green with yellow
stripe) to the board (see Figure 1) and cabinet. The
earth ground wire will connect to the upper hinge
when using the large enclosure and to the lower
hinge on the small enclosure.
Figure 1
S5832SG PCB Terminal Layout
Panel Setup and Installation
The first step in any installation process is careful planning
of the installation. Install the Sierra Model S5832SG in a
location as close as possible to power and phone lines. The
control panel is designed to operate as a local panel, with an
optional plug-on digital communicator.
Earth Ground
To ensure the effectiveness of the lightning and transient
protection circuits, the control panel must be connected to
"Earth Ground". Ideally, this should be a common ground to
the power lines, telephone system, and security system.
This type of ground, called a "Unified Earth Ground", pro-
vides the best protection. The ground connection, from a
grounding rod, cold water pipe or other established ground
point, is made to the green/yellow jacketed wire, providing a
ground to the panel housing.
Power
Lines
Control
Panel
Unified Earth Ground
with Bonded Ground Roots
Telephone
Earth Ground
Power Line
Earth Ground
Telephone
Lines
Figure 2
Connecting to
Earth Ground
Nylon retaining
screw