Sierra S5832SG Video Game Controller User Manual


 
i
Country Specific Compliance Information
Singapore
The following hardware and programming guidelines are required
for installation of this system in Singapore.
Hardware Requirements:
1. The Digital Communicator must be Model S5070SG or S5070SG-2.
Programming Requirements:
1. Dial Type (Block 4, CL 101) must be programmed for DTMF only.
2. Dial Attempts (Block 4, CL 102) must not be programmed to more
than 10.
AH Requirements for Backup
Product/Device 4-Hour 24-Hour 72-Hour Qty Total
S5832SG 0.5 AH 3.0 AH 9.0 AH
S5010 0.12 AH 0.72 AH 2.16 AH
S5020 0.12 AH 0.72 AH 2.16 AH
S5030 0.12 AH 0.72 AH 2.16 AH
S5050 0.4 AH 2.4 AH 7.2 AH
S5058 0.16 AH 0.96 AH 2.88 AH
S5070(-2) 0.14 AH 0.84 AH 2.52 AH
SN915-BUS 0.5 AH 3.0 AH 9.0 AH
Sensor (10 mA) 0.04 AH 0.24 AH 0.72 AH
Sensor (25 mA) 0.1 AH 0.6 AH 1.8 AH
Bell/Siren (5 min) 0.085 AH 0.085 AH 0.085 AH
Bell/Siren (15 min) 0.225 AH 0.225 AH 0.225 AH
* Bell/Siren current may be 0.7 - 1.0 A Total AH Required
Table B - AH Requirements
Determining Standby Battery Requirements
To calculate the size (AH rating) of your system's Backup Battery,
enter the Number (Qty) of devices of each type in the chart above.
Multiply the number of devices times the AH rating for the desired
backup period (Qty x AH = Total) and enter the total in the last
column. To determine the total AH rating of the battery, add all
values in the last column.
Total current from all sensors must be considered when calculat-
ing AH rating. For example:
10 sensors @ 10 mA = 100 mA
4 sensors @ 25 mA = 100 mA
Total current all sensors = 200 mA
Malaysia
The following hardware and programming guidelines are required
for installation of this system in Malaysia.
Hardware Requirements:
1. The Digital Communicator must be Model S5070SG or S5070SG-2.
Programming Requirements:
1. Dial Attempts (Block 4, CL 102) must not be programmed to more
than 3.
Standby Battery Information
The Table and worksheet below provide the installer with the infor-
mation necessary to determine the AH rating and battery require-
ments for any particular installation.
Sierra Accessory Loading
Product current consumption Max. Standby Max. Active
S5832 Control Panel 125 mA 125 mA
S5010 Alpha Keypad 30 mA 50 mA
S5020 LED Keypad 30 mA 50 mA
S5030 Icon Keypad 30 mA 50 mA
S5050 REMM (up to 2) 100 mA (each) 100 mA
S5058 ZEM (up to 3) 40 mA (each) 40 mA**
S5070 Single-line Dialer 35 mA 60 mA
S5070-2 Dual-line Dialer 35 mA 70 mA
SN915-BUS RF Receiver 125 mA 170 mA
**ZEM VOUT terminals can supply up to 300 mA (max.)
Table A - Standby Battery Loading