Sierra S5832SG Video Game Controller User Manual


 
32
Comments
If enabled, jumps to the last 5 seconds of the exit delay,
then arms the system. Requires a normally open switch
connected to keypad (TXD and C terminals).
Exit Delay Terminator
Cmd Loc 012
Default 1
Range 1 - 2
Block 7 - Auxiliary Devices Programming (cont.)
Options:
1No
2Yes
Timer Units (On Board Relay)
Cmd Loc 013
Default 2
Range 1 - 5
Timer Count (On Board Relay)
Cmd Loc 014
Default 30
Range 1 - 255
Comments
Each relay has its own independent countdown timer.
The timer consists of two parts: the Units and the Counter.
The countdown timer determines the amount of time a
relay will remain closed. For the On-Board Relay, CL 013
stores the units, while CL 014 stores the starting count.
The timer will count backwards and when it reaches 0,
the respective relay will open.
Options:
1 Latched
2 Seconds
3 Minutes
4 Hours
5 Days
Timer Units (REMM #1, Relay #1)
Cmd Loc 015
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #1)
Cmd Loc 016
Default 30
Range 1 - 255
Comments
For REMM #1, Relay #1, CL 015 stores the units, while
CL 016 stores the starting count. The timer will count
backwards and when it reaches 0, the respective relay
will open.
Timer Units (REMM #1, Relay #2)
Cmd Loc 017
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #2)
Cmd Loc 018
Default 30
Range 1 - 255
Comments
For REMM #1, Relay #2, CL 017 stores the units, while
CL 018 stores the starting count. The timer will count
backwards and when it reaches 0, the respective relay
will open.
Timer Units (REMM #1, Relay #3)
Cmd Loc 019
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #3)
Cmd Loc 020
Default 30
Range 1 - 255
Comments
For REMM #1, Relay #3, CL 019 stores the units, while
CL 020 stores the starting count. The timer will count
backwards and when it reaches 0, the respective relay
will open.
Timer Units (REMM #1, Relay #4)
Cmd Loc 021
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #4)
Cmd Loc 022
Default 30
Range 1 - 255
Comments
For REMM #1, Relay #4, CL 021 stores the units, while
CL 022 stores the starting count. The timer will count
backwards and when it reaches 0, the respective relay
will open.
Timer Units (REMM #1, Relay #5)
Cmd Loc 023
Default 2
Range 1 - 5
Timer Count (REMM #1, Relay #5)
Cmd Loc 024
Default 30
Range 1 - 255
Comments
For REMM #1, Relay #5, CL 023 stores the units, while
CL 024 stores the starting count. The timer will count
backwards and when it reaches 0, the respective relay
will open.
NOTE: The timer function is ignored if the Relay option (Block 7, CL 001 -
011) is programmed for SpreadNet Arming/Disarming (option #5), Listen-In
Trigger (option #9), Follows Keypad Sounder (option #10), Relay Status #1
(option #67), Relay Status #2 (option #68), 3-second Toggle for Audible
Shutoff (option #72), or 3-second Toggle for Local Bell Test (option #73).