Sierra S5832SG Video Game Controller User Manual


 
23
Comments
The selected outputs will sound for three sec-
onds following a successful closing report.
Ringback Outputs Enable
Cmd Loc 115
Default 0
Range 0 - 15
Options:
0 Disable
1 Keypad Buzzer
2 Strobe
4 Internal Siren
8 External Bell
Phone Line Call Routing
Cmd Loc 112
Default 1
Range 1 - 4
Options:
1 Line #1 Only
2 Line #1 with Line #2 Backup
(Phone Line Cut or Comm
Fail)
3 Line #1 with Line #2 as Backup,
Alternating (2 Attempts Each)
4 Line #1 with Line #2 as Backup,
Alternating (4 Attempts Each)
Comments
This option determines the test interval. Test reports are sent in daily
intervals, ranging from 1 to 30 days. The time of day for the report is
programmed into Block 4, CL 114. To disable reporting, set to 0.
Test Report Interval (Days)
Cmd Loc 113
Default 7
Range 0 - 30
Comments
When programming the test report time of day, use the 24-hour format.
(Add 12 hours for afternoon and evening times.)
Test Report Time of Day (Hours)
Cmd Loc 114
Default 1
Range 0 - 23
Block 4 - Digital Communicator Programming (cont.)
Comments
Establishes the modem protocol for RPS and CFSK-IV
communications.
RPS and CFSK-IV Modem Type
Cmd Loc 107
Default 2
Range 1 - 2
Options:
1 Bell 103
2 CCITT
Comments
The delay (in seconds) after an alarm occurs before the report is sent.
Alarm Dialing Delay (Seconds)
Cmd Loc 108
Default 0
Range 0 - 255
Comments
If enabled, uses the time programmed above (Block 4, CL
108) for reporting alarms on 24-hour zones. If disabled, 24-
hour zones report immediately.
24-Hour Zone Dial Delay
Cmd Loc 109
Default 1
Range 1 - 2
Comments
The amount of time (in seconds), following an alarm, during which a cancel
report may be sent. The cancel report is not sent if a valid user code is
entered before the alarm dialing delay has expired.
Cancel Report Delay (Seconds)
Cmd Loc 110
Default 0
Range 0 - 255
Options:
1No
2Yes
Dialer Retry Sequence
Cmd Loc 111
Default 4
Range 1 - 4
Options:
1 Repeat Call Attempt
Series Every 30 min.
2 Repeat Call Attempt
Series Every four hrs.
3 Repeat Call Attempt Series at 30 min.
then double interval up to 128 hrs.
4 No additional Call Attempts After Failed
Series Until New Report is Queued.
Comments
If enabled, requires the panel to call COMMANDER II in
order to establish RPS. If disabled, the panel will stay on-line
when called by COMMANDER II the second time (following
handshaking).
RPS Callback Enable
Cmd Loc 105
Default 1
Range 1 - 2
Options:
1No
2Yes
Comments
If enabled, allows remote programming to be initiated from
the keypad (either Block 0 or user programming).
Keypad RPS Enable
Cmd Loc 106
Default 2
Range 1 - 2
Options:
1No
2Yes