Sierra S5832SG Video Game Controller User Manual


 
29
Comments
These two-digit report codes indicate tamper, trouble, and restoral con-
ditions associated with hardwired keypads. When using single-digit
reporting formats, only the second digit is sent.
Report Code, Keypad Tamper
Cmd Loc 173 174
Default 0 1
Range 0 - 15 (All CL)
Report Code, Keypad Tamper Restoral
Cmd Loc 175 176
Default 0 1
Range 0 - 15 (All CL)
Report Code, Keypad Trouble
Cmd Loc 177 178
Default 0 0
Range 0 - 15 (All CL)
Report Code, Keypad Trouble Restoral
Cmd Loc 179 180
Default 0 0
Range 0 - 15 (All CL)
Block 5 - Reporting Digits Programming (cont.)
Report Code, Accessory Tamper
Cmd Loc 169
Default 1
Range 0 - 15
Report Code, Accessory Tamper Restoral
Cmd Loc 170
Default 1
Range 0 - 15
Comments
The respective report code is sent to indi-
cate a tamper or trouble condition (or the
respective restoral report) associated with
a specific accessory. For two-digit report-
ing formats, a hardcoded address is
added as the second digit. The addresses
for each accessory are listed to the right.
Report Code, Accessory Trouble
Cmd Loc 171
Default 1
Range 0 - 15
Report Code, SpreadNet Keypad/Keyfob Low
Battery Restoral
Cmd Loc 168
Default 1
Range 0 - 15
Report Code, Accessory Trouble Restoral
Cmd Loc 172
Default 1
Range 0 - 15
Accessory Addresses
1 - ZEM #1
2 - ZEM #2
3 - ZEM #3
4 - Not Used (Reserved)
5 - REMM #1
6 - REMM #2
7 - SN915-BUS Receiver
Comments
This two-digit report code will indicate that the report buffer has over-
flowed. When using single-digit reporting formats, only the second digit is
sent.
Report Code, Report Queue Overflow
Cmd Loc 163 164
Default 0 0
Range 0 - 15 (All CL)
Report Code, SN Keypad Supervisory Failure
Cmd Loc 165
Default 1
Range 0 - 15
Report Code, SN Kpd Supervisory Fail Restoral
Cmd Loc 166
Default 1
Range 0 - 15
Report Code, SpreadNet Keypad/Keyfob Low
Battery
Cmd Loc 167
Default 1
Range 0 - 15
Comments
The SpreadNet keypad supervisory (check-in) failure and restoral report
codes are a single-digit code. For two-digit reporting formats, the keypad
address is sent as the second digit. To disable reporting, program 0 into
the specific location.
Comments
These report codes apply to the SpreadNet keypad, remote, and keyfob.
The low battery and restoral report codes are a single-digit code. For two-
digit reporting formats, the respective keypad number or user number
associated with the remote/keyfob will be sent as the second digit. To
disable reporting, program 0 into the specific location.