Sierra S5832SG Video Game Controller User Manual


 
34
Comments
These Options will determine the Day(s) of
the Week and Time of Day when the pro-
grammed relay will automatically close. The
value programmed into CL 067 is the total for
all days the relay is to be activated. The relay
to be closed is programmed in Block 7, CL
001 - 011 using Option 79.
Once activated, the relay will remain closed
for the amount of time programmed into the
countdown timer for the specific relay (Block
7, CL 013 - 034).
Timed Relay Closing (Timer #1 - Day of Week)
Cmd Loc 067
Default 0
Range 0 - 127
Timed Relay Closing (Timer #1 - Hours)
Cmd Loc 068
Default 0
Range 0 - 23
Timed Relay Closing (Timer #1 - Minutes)
Cmd Loc 069
Default 0
Range 0 - 59
Options: (CL 067)
0 Disabled
1 Saturday
2 Friday
4 Thursday
8 Wednesday
16 Tuesday
32 Monday
64 Sunday
Block 7 - Auxiliary Devices Programming (cont.)
Comments
These Options will determine the Day(s) of
the Week and Time of Day when the pro-
grammed relay will automatically close. The
value programmed into CL 070 is the total for
all days the relay is to be activated. The relay
to be closed is programmed in Block 7, CL
001 - 011 using Option 80.
Once activated, the relay will remain closed
for the amount of time programmed into the
countdown timer for the specific relay (Block
7, CL 013 - 034).
Timed Relay Closing (Timer #2 - Day of Week)
Cmd Loc 070
Default 0
Range 0 - 127
Timed Relay Closing (Timer #2 - Hours)
Cmd Loc 071
Default 0
Range 0 - 23
Timed Relay Closing (Timer #2 - Minutes)
Cmd Loc 072
Default 0
Range 0 - 59
Options: (CL 070)
0 Disabled
1 Saturday
2 Friday
4 Thursday
8 Wednesday
16 Tuesday
32 Monday
64 Sunday
Comments
These Options will determine the Day(s) of
the Week and Time of Day when the pro-
grammed relay will automatically close. The
value programmed into CL 073 is the total for
all days the relay is to be activated. The relay
to be closed is programmed in Block 7, CL
001 - 011 using Option 81.
Once activated, the relay will remain closed
for the amount of time programmed into the
countdown timer for the specific relay (Block
7, CL 013 - 034).
Timed Relay Closing (Timer #3 - Day of Week)
Cmd Loc 073
Default 0
Range 0 - 127
Timed Relay Closing (Timer #3 - Hours)
Cmd Loc 074
Default 0
Range 0 - 23
Timed Relay Closing (Timer #3 - Minutes)
Cmd Loc 075
Default 0
Range 0 - 59
Options: (CL 073)
0 Disabled
1 Saturday
2 Friday
4 Thursday
8 Wednesday
16 Tuesday
32 Monday
64 Sunday
Comments
These Options will determine the Day(s) of
the Week and Time of Day when the pro-
grammed relay will automatically close. The
value programmed into CL 076 is the total for
all days the relay is to be activated. The relay
to be closed is programmed in Block 7, CL
001 - 011 using Option 82.
Once activated, the relay will remain closed
for the amount of time programmed into the
countdown timer for the specific relay (Block
7, CL 013 - 034).
Timed Relay Closing (Timer #4 - Day of Week)
Cmd Loc 076
Default 0
Range 0 - 127
Timed Relay Closing (Timer #4 - Hours)
Cmd Loc 077
Default 0
Range 0 - 23
Timed Relay Closing (Timer #4 - Minutes)
Cmd Loc 078
Default 0
Range 0 - 59
Options: (CL 076)
0 Disabled
1 Saturday
2 Friday
4 Thursday
8 Wednesday
16 Tuesday
32 Monday
64 Sunday
Comments
This option determines where panel events are stored.
0 = No REMMs installed, all events are stored in the
control panels event memory (60 events maxi-
mum).
1 = REMM #1 installed. Control panel events will be
stored in the REMM (250 events maximum).
2 = Both REMM #1 and REMM #2 are installed.
Control panel events will be stored using a both
REMMs (500 events maximum).
Number of REMMs
Cmd Loc 079
Default 0
Range 0 - 2
Options:
0 None
1 REMM 1 only
2 REMM 1 and 2