Honeywell MS4103 Video Gaming Accessories User Manual


 
95
Fire And Smoke Actuator
MS4209F; MS4309F; MS4709F; MS4809F; MS8209F; MS8309F
SUBMITTAL SHEETS
MS4209F; MS4309F; MS4709F; MS4809F; MS8209F; MS8309F
Spring return direct coupled
actuators (DCA) for on/off damper
control with an integral junction box.
The actuator accepts an on/off signal
from a single-pole, single-throw
(SPST) controller. They are designed
to operate reliably in smoke control
systems requiring Underwriter's
Laboratories Inc. UL555S ratings up
to 350 F.
SPECIFICATIONS
Actuator Type .......................................Damper
Rotational Stroke ..................................95 ±3 degrees
Fail Safe Mode .....................................Spring Return
Rated Torque ........................................80 lb-in. (9 Nm)
Maximum Stall Torque ..........................240 lb-in. (27 Nm)
Minimum Driving Torque at 350 F ........80 lb-in. (9 Nm)
Spring Return Torque ...........................80 lb-in. (9 Nm)
External Auxiliary Switches Available ..Yes, 32003532-005
Electrical Connections .........................Two color-coded leads
Electrical Connection Length ...............16 in. (406 mm)
Environmental Rating ...........................NEMA1
Frequency ............................................60 Hz
Mounting ..............................................Direct Coupled
Maximum Noise Rating,
Holding (dBA @ 1m) ............................20 (no audible noise)
Maximum Noise Rating,
Driving (dBA @ 1m) ..............................80
Compatible Damper Shafts .................. 3/8 to 1/2 in. square or round
(10 to 13 square/round)
Shaft Adapter Type ..............................Aluminum Hub, four set screws
Supply Voltage .....................................120 Vac +10%, -15%
Materials ...............................................Aluminum housing
Operating Humidity Range (% RH) ......5 to 95% RH, non-condensing
Ambient Temperature Range ...............0 F to 130 F (-18 C to 55 C)
Storage Temperature Range ................-40 F to 140 F (-40 C to 60 C)
Weight .................................................. 6 lb (2.72 kg)
Comments ............................................Integral junction box with three
7/8 in. conduit openings
(fittings not included)
APPROVALS
CE .........................................................89/336/ECC, 73/23/EEC
C-Tick ...................................................N314
Underwriters Laboratories, Inc. ............UL873, Plenum Rated
Canadian Underwriters Laboratories, Inc. cUL C22.2 No. 24-93
FEATURES
Integral spring return ensures level of return torque.
Fifteen-second spring return timing.
No special cycling required during long-term holding.
No audible noise during holding.
Patent pending design eliminates need for limit switches to
reduce power consumption.
Models available for 24, 120, and 230 Vac.
Ninety-five degree angle of rotation for tight damper
closure.
Actuator holds rated torque at reduced power level.
Die-cast aluminum housing. Housing design allows flush
mounting to damper.
Integral junction box with three conduit openings eliminates
need for separate wiring box.
High-temperature indicator included.
DIMENSIONS DIAGRAM
2 (51)
1 (25)
5/8
(17)
6 3/8
(161)
7 1/2
(192)
4 (102)
7/8 (22)
5 1/8 (129)
2 (51) 3 5/16 (84)
1/16 (2)
M17508