Honeywell MS4103 Video Gaming Accessories User Manual


 
114
Q7130; Q7230; Q7330
For converting Series 90
Modutrol IV motors to Series 70
(electronic) control.
SPECIFICATIONS
Application Type ..................................Damper
Dimensions, Approximate .................... Fits inside wiring junction box
of Modutrol IV Motor
Control Signal ....................................... Provides selectable voltage
ranges: 4 to 7, 6 to 9, or 10.5 to
13.5 Vdc. Adapts M91XX to
function as M71XX model
Electrical Connections .........................Terminal Board
Frequency ............................................ 50 Hz; 60 Hz
Mounting ..............................................Mounts to quick-connects
inside Mod Motor
Ambient Temperature Range ............... -40 F to 150 F (-40 C to 60 C)
Weight ..................................................0.3 lb
FEATURES
Mounts and works inside wiring box of any series 90
Modutrol IV Motor.
Protected from weather by motor's NEMA 3 wiring box.
Mates to motor's quick-connect terminals and provides
screw terminals for control wiring connections.
Features solid-state circuitry with surface mount
components.
Cover holds module in place, screws not required.
Includes (except Q7330A) reversing switch to allow
replacement of electrically normally open or electrically
normally closed motors.
Modutrol IV Motor
Q7130; Q7230; Q7330