Honeywell MS4103 Video Gaming Accessories User Manual


 
56
NPT Globe Valves ½- 3"
With Pneumatic Actuators
Common Features
• Rolling diaphragm for long life and
low hysteresis
• Easily installation and attachment
to the valve
• Direct or reverse acting
• No positive positioner
Actuator Features Without Positive Positioner
Actuator O.S. Number
MP953C1000
MP953C1018
MP953C1026
MP953C1067
MP953C1075
MP953C1083
MP953C1554
MP953C1562
MP953D1107
MP953D1131
MP953D1172
Direct / Reverse Acting DA / RA DA DA DA DA DA DA DA DA RA RA RA
Diaphragm Size
5" 5" 5" 8" 8" 8" 13" 13" 7-1/8" 7-1/8" 7-1/8"
Fail Safe Action
Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Down Stem Down Stem Down
Positioner 10psi span
N/A5psi span
3psi span
Valve Size
(inches)
Cv
Flow
Characteristic
Valve
Action
Valve OS
Number
Close-off Pressure - See Charts On Page 51
2-Way
Water Valves
Straight Through
2.9
Equal %
Stem up to
close
V5011N3004
A-NC A-NC A-NC B-NC B-NC B-NC
N/A
C-NO C-NO C-NO
1/2" 4.7
V5011N3012
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
3/4" 7.3
V5011N3020
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1" 11.7
V5011N3038
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1-1/4" 18.7
V5011N3046
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1/2" 0.73
Stem down
to close
V5011N1008
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 1.16
V5011N1016
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 1.85
V5011N1024
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 2.9
V5011N1032
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 4.7
V5011N1040
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
3/4" 7.3
V5011N1057
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1" 11.7
V5011N1065
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1-1/4" 18.7
V5011N1073
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1-1/2" 29.3
V5011N1081
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
2" 46.8
V5011N1099
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
2-1/2" 63
V5011F1105
L-NO L-NO L-NO L-NO L-NO L-NO G-NC G-NC G-NC
3" 100
V5011F1113
L-NO L-NO L-NO L-NO L-NO L-NO
G-NC G-NC G-NC
2-Way
Steam Valves
Straight Through
1/2" 0.73
Linear
Stem down
to close
V5011N2006
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO
N/A
D*-NC D*-NC D*-NC
1/2" 1.16
V5011N2014
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 1.85
V5011N2022
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 2.9
V5011N2030
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 4.7
V5011N2048
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
3/4" 7.3
V5011N2055
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1" 11.7
V5011N2063
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1-1/4" 18.7
V5011N2071
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1-1/2" 29.3
V5011N2089
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC
D*-NC
2" 46.8
V5011N2097
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
2-1/2" 63
V5011G1111
L*-NO L*-NO L*-NO L*-NO L*-NO L*-NO G*-NC G*-NC G*-NC
3" 100
V5011G1129
L*-NO L*-NO L*-NO L*-NO L*-NO L*-NO G*-NC G*-NC G*-NC
3-Way
Water Valves
Mixing
1/2" 2.9
Linear B-AB /
Equal % A-AB
Stem up
closes A-AB
V5013N1030
H-NC H-NC H-NC J-NC J-NC J-NC
N/A
K-NC K-NC K-NC
1/2" 4.7
V5013N1048
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
3/4" 7.3
V5013N1055
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1" 11.7
V5013N1063
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1-1/4" 18.7
V5013N1071
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1-1/2" 29.3
V5013N1089
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
2" 46.8
V5013N1097
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
*The close-off pressure not to exceed rated pressure of steam valve
NC = Normally Closed
NO = Normally Open
SPRING RANGE PSI (kPa)
L - LOWER SEAT
U - UPPER SEAT
ACTUATOR AIR PRESSURE IN PSI (kPa)
4-11
(30-75)
11
(75)
12
(85)
13
(90)
14
(95)
15
(105)
16
(110)
17
(115)
18
(125)
4
(30)
3
(20)
2
(15)
1
(5)
0
(0)
LU
V5013N: 1/2-INCH TO 2-INCH VALVE BODIES WITH
5-INCH DIRECT ACTING PNEUMATIC ACTUATOR
5
(35)
10
(70)
15
(105)
20
(140)
25
(170)
30
(205)
35
(240)
40
(275)
CLOSEOFF PRESSURE RATING - PSI (kPa)
2-7
(15-50)
7
(50)
8
(55)
9
(60)
10
(70)
11
(75)
12
(85)
13
(90)
14
(95)
2
(15)
1
(5)
0
(0)
LU
MIXING
1
1
USE 4-11 PSI (30-75 kPa) RANGE FOR DETERMINING CLOSEOFF OF VALVES WITH
MP953E ACTUATORS.
M12909
8-12
(55-85)
12
(85)
13
(90)
14
(95)
15
(105)
16
(110)
17
(115)
18
(125)
1
(5)
8
(55)
7
(50)
6
(40)
LU
5
(35)
4
(30)
3
(20)
2
(15)
45
(310)
55
(380)
65
(450)
50
(345)
60
(415)
70
(485)
Cv 2.9
Cv 4.7
Cv7.3
Cv 11.7
Cv18.7
Cv 29.3
Cv 46.8
Chart H