164
Foot Mounted Motors
M6274, M6284, M6285, and M6294 Motors with Linear 10K Feedback
Typical wiring for Series 62 motors
M7164, M7284, M7285, M7286, and M7294
Typical wiring for Series 70 motors
M7685
Typical wiring for M7685 motors
R
B
W
R
1
2
T
G
Y
4
3
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
TRANSFORMER MAY BE INTERNAL OR EXTERNAL
TO MOTOR.
FEEDBACK POTENTIOMETER.
M17096
SERIES 60
CONTROLLER
SERIES 62
MOTOR
1
2
3
1
2
3
CONTROLLER
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.
CONNECTING F TO – WILL DRIVE MOTOR TO FULLY OPEN.
1
M5778
1
-
MOTOR
2
F
T1
T2
2
+
-
+
24V
1
2
3
T1
T2
C
R
4
3
1
L1
L2
(HO T)
+
-
2
2
3
DAMPER MOTORS
WHITE
RED
MODULATING
dc VOLTAGE
SOURCE
MINIMUM
POSITION
POTENTIOMETER
EXTERNAL
CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLAOD PROTECTION AS REQUIRED.
IF MINIMUM POSITION POTENTIOMENTER IS NOT USED,
JUMPER TERMIALS 3 AND 4.
TRANSFORMER MAY BE INTERNAL OR EXTERNAL.
M13727
Actuator Wiring Diagrams
Foot Mounted Motors