63
Specifications
|
Specifications
This chapter provides the following specifications:
S Model list
S Dimensions and weights
S Electrical input and output
S Environmental and safety
S Battery
S UPS block diagram
Table 10. UPS Model List
120V Models 208V Model 230V Models
UPS Models 2700R Telco LV (K803N),
2700W
2700R Telco HV-US
(H950N), 2700W
2700R Telco HV (J728N),
2700W
External Battery Module
(EBM)
2700R EBM (H967N), 96 Vdc
Table 11. Dimensions and Weights
UPS EBM Model
UPS Dimensions
(W H D)
438.0 171.5 433.0 mm
17.2” 6.8” 17.0” (4U)
438.0 171.5 433.0 cm
17.2” 6.8” 17.0” (4U)
Weights 36.9 kg (81.4 lb) 51.8 kg (114.2 lb)
Table 12. Electrical Input
120V Models 208V Models 230V Models
Nominal Voltage 120V 208V 230V
Voltage Range 82–144V auto-sensing 155–255V auto-sensing 160–286V auto-sensing
Nominal Frequency 50/60 Hz auto-sensing, ±3 Hz
Efficiency (Normal Mode) >95%
Noise Filtering Full-time EMI/RFI filtering
Connections 2m, L5-30P attached
power cord
IEC 320-C20 input
connector, 16A
IEC 320-C20 input
connector, 16A
7