UPS Initial Startup
To start up the UPS:
1 Verify that the internal batteries are connected.
2 If an optional EBM is installed, verify that the EBM is connected to the UPS.
3 Verify that the power input to the UPS has adequate upstream overcurrent protection:
Table 1. Minimum Upstream Circuit Breaker Rating
UPS Output Power
120V 208V 230V
2700W 30A 20A 16A
The power cord current ratings are listed in Table 2.
Table 2. Power Cord Ratings
Dell UPS Model and Voltage
Power Cord Rating Country Supplied Cord Set
2700W 208V
L6-20P to C19 15A North America Yes
C19 to C20 Jumper 16A North America Optional
2700W 230V
CEE 7/7 Schuko to C19 16A Europe (Schuko) Yes
BS 1363 to C19 13A United Kingdom (New) Yes
GB2009.1 to C19 16A China Yes
C19 to C20 Jumper 16A Europe/Australia Yes
C19 to C20 Jumper 16A China Yes
BS 546 to C19 15A United Kingdom(Old) Optional
TI16S3 to C19 16A Thailand Optional
AS 3112 to C19 15A Australia Optional
IRAM2073 to C19 16A Argentina Optional
CEI 23-50 to C19 16A Italy Optional
KSC8305 to C19 15A South Korea Optional
IS 1293 to C19 16A India Optional
NBR 14136 to C19 16A Brazil Optional
C19 to C20 Jumper 16A North America Optional
L6-20P to C19 15A North America Optional