Trane PID Control Video Game Controller User Manual


 
®
Chapter 5 Troubleshooting
46 CNT-APG002-EN
Tips for specific problems
Table 17 provides tips for troubleshooting specific problems.
Changing the sampling frequency
The major cause of actuator cycling is time lags in the system. If a 10%
change in PID output requires two minutes to affect the measured vari-
able, it does no good to have the sampling frequency set to two seconds.
The integral contribution will build up before any significant change in
error can be measured. A sampling frequency of 30 to 60 seconds would
work much better in this situation. In other words, to fix a cycling system,
slow down the loop. See Sampling frequency on page 12 for more infor-
mation.
Changing the gains
Be careful when changing PID gains. Never change the gains unless the
effects can be measured. Use a doubling/halving technique when increas-
ing or decreasing gains. If the PID gains are set to 4, 1, and 0 respectively,
and you are going to reduce them, try 2, 0.5, and 0. If the system now
undershoots, try gains of 3, 0.75, and 0 respectively. Refer to Throttling
range on page 9 for more information.
Ta b le 17 : Tips for specific problems
Problem Tips
Measured variable is
cycling around setpoint
Slow the sampling frequency
Decrease PID gains
Check programming for conflicting actuator
commands
Actuators may be overridden by minimum-on
and -off times
Overshooting setpoint Reduce gains
Undershooting setpoint Increase gains
Output at maximum Ensure that minimum output is not set to 100%
Output at minimum Ensure that maximum output is not set to 0%