Trane PID Control Video Game Controller User Manual


 
®
Chapter 3 Programming PID loops
26 CNT-APG002-EN
Programming in TGP
Figure 17 shows the PID block used to program PID loops in TGP editor.
The PID block is more flexible than the DDC function in PCL. The enable/
disable and failure inputs can accept any binary value, regardless of
source. The setpoint, measured variable, p-gain, i-gain, and d-gain inputs
can accept any analog value, except analog outputs, including variable
(local or from a BAS), hardware input, and network input. You can pro-
gram PID settings in the PID Properties dialog box, shown in Figure 18.
Figure 17: TGP PID block
Figure 18: PID Properties dialog box
Binary value
Output: analog value
Analog value