Mitsubishi Electronics FX3U-CF-ADP Video Gaming Accessories User Manual


 
8 CF-ADP Applied Instructions Explanation
8.8 FNC 305 - FLSTRD / FX3U-CF-ADP status read
78
FX3U-CF-ADP User's Manual
When is "K768 (H300)"
The FLSTRD instruction reads the version information of the CF-ADP.
When is "K1024 (H400)"
The FLSTRD instruction reads the error information (error flag).
When is "K1280 (H500)"
The FLSTRD instruction reads the error code and error code details for errors having occurred in the CF-
ADP. Up to 5 of the latest error codes and error code details can be stored.
Program Example
1) Program Example 1
When X000 turns ON, the FLSTRD instruction reads the status information. D100 stores the final line
position of a file whose ID is "1", and D101 stores the final digit position.
Channel number 1 is used.
Setting items Description
Stores the version of CF-ADP.
(Example) K100 = Ver.1.00
Setting items Description
Error detection signal
b0 : The CompactFlash
TM
card is not mounted.
b1 : The CompactFlash
TM
card is full.
b2 : An error has occurred in the CF-ADP.
b3 : CF-ADP H/W error
b4 : CompactFlash
TM
card error
b5 to b15 : Not used
Setting items Description
Error code 1
+1
Error code details 1
+2
Error code 2
+3
Error code details 2
+4
Error code 3
+5
Error code details 3
+6
Error code 4
+7
Error code details 4
+8
Error code 5
+9
Error code details 5
S
D
S
D
S
D
D
D
D
D
D
D
D
D
D
X000
M0SET
M0
FNC305
FLSTRD
D0 K1K1
M8029
D100D0
D101D1
FNC 12
MOV
FNC 12
MOV
Execution
completion
M8329
Abnormal end
M0RST