7 Before Programming
7.4 General Rules for Applied Instructions
45
FX3U-CF-ADP User's Manual
1
Introduction
2
Specification
3
System
Configuration
4
Installation
5
Wiring
6
Functions
7
Before
Programming
8
CF-ADP Applied
Instructions
Explanation
9
Program
Examples
10
Troubleshooting
2) To use at a position other than just below the CF-ADP instructions.
If two or more CF-ADP instructions are used in a program, the "Instruction execution complete" flag
(M8029) and "Instruction execution abnormal end" flag (M8329) will be turned on or off after execution of
each instruction.
If it is necessary to use the "Instruction execution complete" flag (M8029) or "Instruction execution
abnormal end" flag (M8329) at a point other than just below the instruction, turn on or off another bit
device just below the instruction, and use the contact as the command contact.
M8000
FNC 72
DSW
X10 Y10 D0 K1
FNC 22
MUL
D0 K10 D20
M8029
Completion
of instruction
execution
M0
FNC300
FLCRT
K1 D0 D10
M8029
Completion
of instruction
execution
Switches "instruction
execution complete"
flag of the DSW
instruction from M8029
to M100.
M100
M200
Switches the
"instruction execution
complete" flag of the
FLCRT instruction from
M8029 to M200.
M100
Functions as the instruction
execution complete flag of
the DSW instruction.
RST
M0
M200
Functions as the instruction
execution complete flag of the
FLCRT instruction.
Y000
K1